Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 13, 2020, 01:01 PM
  • 18 1111_18 1110 _07132020_060926.mp4

Date
07/13/2020
W/O
829136
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00710
PipeID
P14957
Time
6:01 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7875
Sewer Name
18 SO WHITTIER OUTFALL RLF TR, SECTS 2E&2F
City
WHITTIER
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
26
Purpose
Routine Assessment
Project
WO_829136_TV18149_MAY2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
33 in.
Upstream MH
18 1110
Downstream MH
18 1111
Dir. of Survey
Upstream
Length Surveyed
13 ft.
Total Length
13 ft.
Structural Index
3
Structural Quick
3222
Structural Rating
10
O&M Index
3
O&M Quick
4122
O&M Rating
8
Overall Index
3
Overall Quick
Overall Rating
18
Pipe schematic from manhole 18 1110 to 18 1111
MH: 18 1110MH: 18 1111upstream0 ft. AMH - Upstream Manhole, Survey Ends - 18 11110 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/2.9 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish2.9 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish2.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish11 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start11 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start11 ft. MGO - General Observation - 75% MAG COAT11 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start13 ft. MGO - General Observation - CONN @ MH 10 O'CLOCK/ACTIVE13 ft. AMH - Downstream Manhole, Survey Begins - 18 111013 ft. MGO - General Observation - ROACHES @ MH13 ft. MWM - Water Mark, 35 %of cross sectional area13 ft. MWL - Water Level, 30 %of cross sectional area

Observation photos (4)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - CONN @  MH 3 O'CLOCK/

    13 ft. - General Observation - CONN @ MH 3 O'CLOCK/

Observations (14)

DistanceCodeObservation
2SAP
0MGOCONN @ MH 10 O'CLOCK/ACTIVE
0AMH18 1110
10.1SSS
13AMH18 1111
0MGOROACHES @ MH
2DAGS
10.1SAP
0MWM
0MWL
2MGO75% MAG COAT
2SSS
13MGOCONN @ MH 3 O'CLOCK/
10.1DAGS

Properties (7)

additional_info
SC411714
custom_field_two
2
customer
LACSD
datetime
2020-07-13T06:01:44-07:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
27635