- Date
- 07/13/2020
- W/O
- 829136
- Weather
- Dry
- Operator/Surveyor
- S. LOPEZ
- Sewer ID
- Z00710
- PipeID
- P14956
- Time
- 6:12 AM
- Certificate
- U-111-11880
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K7875
- Sewer Name
- 18 SO WHITTIER OUTFALL RLF TR, SECTS 2E&2F
- City
- WHITTIER
- Loc. details
- Easement/Right of Way
- Location Code
- D
- Use of Sewer
- Sanitary Sewer
- District
- District 18
- Page No.
- 26
- Purpose
- Routine Assessment
- Project
- WO_829136_TV18149_MAY2020
- Sewer Type
- Gravity
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 33 in.
- Width
- 33 in.
- Upstream MH
- 18 1110
- Downstream MH
- 18 1109
- Dir. of Survey
- Downstream
- Length Surveyed
- 423 ft.
- Total Length
- 423 ft.
- Structural Index
- 3
- Structural Quick
- 3P2P
- Structural Rating
- 420
- O&M Index
- 3
- O&M Quick
- 413P
- O&M Rating
- 423
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 843
Pipe schematic from manhole 18 1110 to 18 1109 Observation photos (3)

0 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start