Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 21, 2020, 10:13 AM
  • 15 0776_15 0775_7212020_033144.mp4

Date
07/21/2020
W/O
0839422
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00593
PipeID
P12977
Time
3:13 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1489R
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 2&5
City
ARCADIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
04
Purpose
Maintenance Related
Project
20200721MDM_ARCADIA_SIERRA_MADRE_TRUNK_SECTS_2_5
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
15 0776
Downstream MH
15 0775
Dir. of Survey
Downstream
Length Surveyed
400.7 ft.
Total Length
400.7 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
3123
O&M Rating
10
Overall Index
2
Overall Quick
Overall Rating
10
Pipe schematic from manhole 15 0776 to 15 0775
MH: 15 0776MH: 15 0775downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MGO - General Observation - MH CONN 3:00 OPEN0 ft. AMH - Upstream Manhole, Survey Begins - 3:45AM29.9 ft. RFJ - Roots Fine Joint, from 07 to 09 o'clock, within 8 inches of joint: YESR - 3% TAP ROOT90 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped94.9 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 5" - Open-100% ROOTS98.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped119 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped122.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped142.7 ft. RMJ - Roots Medium Joint, from 01 to 03 o'clock, 5 %, within 8 inches of joint: YESR - TAP ROOTS142.9 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open=100% ROOTS146.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped167.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped217.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open231.9 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open-100% ROOTS235.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open243.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped250.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Active317.6 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Open400.2 ft. MGO - General Observation - MH CONN 3:00 OPEN400.7 ft. AMH - Downstream Manhole, Survey Ends - 4:10AM

Observation photos (1)

  • Roots Medium Joint, from 01 to 03 o'clock, 5 %, within 8 inches of joint: YESR - TAP ROOTS

    142.7 ft. - Roots Medium Joint, from 01 to 03 o'clock, 5 %, within 8 inches of joint: YESR - TAP ROOTS

Observations (22)

DistanceCodeObservation
29.9RFJ3% TAP ROOT
400.7AMH4:10AM
167.8TFCCapped
90TFCCapped
0MWL
243.8TFCCapped
0MWM
94.9TFDOpen-100% ROOTS
0MGOMH CONN 3:00 OPEN
146.7TFCCapped
235.1TFOpen
217.5TFOpen
122.7TFCCapped
317.6TFOpen
142.7RMJTAP ROOTS
400.2MGOMH CONN 3:00 OPEN
231.9TFDOpen-100% ROOTS
142.9TFDOpen=100% ROOTS
119TFCCapped
0AMH3:45AM
250.4TFActive
98.2TFCCapped

Properties (5)

additional_info
POST ROOT EVALUATION ONLY
customer
LACSD
datetime
2020-07-21T03:13:38-07:00
documentation
MARTIN,OLIVER 111,SHADLER,BARR
is_lateral_inspection
false