Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 5, 2020, 07:14 AM
  • 02 0342_02 0341_06052020_002313.mp4

Date
06/05/2020
W/O
833634
Weather
Dry
Operator/Surveyor
EN. RUIZ
Sewer ID
Z00259
PipeID
P02653
Time
12:14 AM
Certificate
U-116-07001919
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7760
Sewer Name
EAST COMPTON BOULEVARD RELIEF TRUNK
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
36
Purpose
Routine Assessment
Project
RFIR_WO_833634_TV02385_JUN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 0342
Downstream MH
02 0341
Dir. of Survey
Downstream
Length Surveyed
299.8 ft.
Total Length
299.8 ft.
Structural Index
3
Structural Quick
4J3K
Structural Rating
515
O&M Index
2
O&M Quick
2K00
O&M Rating
118
Overall Index
3
Overall Quick
Overall Rating
633
Pipe schematic from manhole 02 0342 to 02 0341
MH: 02 0342MH: 02 0341downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 03422 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start7 ft. FM - Fracture Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES18 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start290 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish295.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Finish297 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish297 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish299.8 ft. AMH - Downstream Manhole, Survey Ends - 02 0341299.8 ft. MGO - General Observation - COCKROACHES IN MH

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: NO, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start

  • Fracture Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES

    7 ft. - Fracture Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    18 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MH

    299.8 ft. - General Observation - COCKROACHES IN MH

Observations (14)

DistanceCodeObservation
0MWL
2CM
0MWM
0AMH02 0342
295.2DAGS
2.1DAGS
18FM
7FM
2SSS
290FM
299.8AMH02 0341
297SSS
297CM
299.8MGOCOCKROACHES IN MH

Properties (7)

additional_info
SC411468
custom_field_three
FRACTURES, GREASE
custom_field_two
3
customer
1
datetime
2020-06-05T00:14:34-07:00
documentation
PRO PIPE
is_lateral_inspection
false