Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 18, 2020, 04:30 AM
  • 02 0338_02 0337_06172020_215011.mp4

Date
06/17/2020
W/O
833634
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00259
PipeID
P02649
Time
9:30 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7733
Sewer Name
EAST COMPTON BOULEVARD RELIEF TRUNK
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
37
Purpose
Routine Assessment
Project
RFIR_WO_833634_TV02385_JUN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
18 in.
Upstream MH
02 0337
Downstream MH
02 0338
Dir. of Survey
Upstream
Length Surveyed
405.1 ft.
Total Length
405.1 ft.
Structural Index
3
Structural Quick
4J3E
Structural Rating
474
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
476
Pipe schematic from manhole 02 0337 to 02 0338
MH: 02 0337MH: 02 0338upstream0 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. AMH - Upstream Manhole, Survey Ends - 02 03380.1 ft. MGO - General Observation - ROACHES @ MH2.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish180.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - ACTIVE182.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES260.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish260.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start265.8 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES300.5 ft. FC - Fracture Circumferential, from 07 to 09 o'clock, within 8 inches of joint: YES351.2 ft. CM - Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES361 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES366.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES401.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES403.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start403.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start405.1 ft. MWM - Water Mark, 15 %of cross sectional area405.1 ft. MWL - Water Level, 15 %of cross sectional area405.1 ft. AMH - Downstream Manhole, Survey Begins - 02 0337

Observation photos (8)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    3.7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    38.4 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    44.1 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

    53.9 ft. - Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

  • Fracture Circumferential, from 07 to 09 o'clock, within 8 inches of joint: YES

    104.6 ft. - Fracture Circumferential, from 07 to 09 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    139.3 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    144.9 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (19)

DistanceCodeObservation
2SSS
2CM
104.6FC
224.2TFACTIVE
222.5DAGS
405.1FM
44.1CL
144.9CM
0MWM
53.9CM
38.4FM
3.7FM
405MGOROACHES @ MH
144.9FM
0MWL
405.1AMH02 0338
0AMH02 0337
139.3FM
403SSS

Properties (7)

additional_info
SC411392
custom_field_three
MULTIPLE CRACKS/ FRACTURES
custom_field_two
2
customer
1
datetime
2020-06-17T21:30:03-07:00
documentation
PROPIPE
is_lateral_inspection
false