Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 18, 2020, 06:01 AM
  • 02 0336_02 0335_06172020_231236.mp4

Date
06/17/2020
W/O
833634
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00259
PipeID
P02647
Time
11:01 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7733
Sewer Name
EAST COMPTON BOULEVARD RELIEF TRUNK
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
37
Purpose
Routine Assessment
Project
RFIR_WO_833634_TV02385_JUN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
18 in.
Upstream MH
02 0336
Downstream MH
02 0335
Dir. of Survey
Downstream
Length Surveyed
348.6 ft.
Total Length
348.6 ft.
Structural Index
4
Structural Quick
4F34
Structural Rating
166
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
166
Pipe schematic from manhole 02 0336 to 02 0335
MH: 02 0336MH: 02 0335downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 03362 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start47.9 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES51 ft. FC - Fracture Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES87.9 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES96.4 ft. CM - Crack Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES141.5 ft. FC - Fracture Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES146.8 ft. FM - Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES151.6 ft. CM - Crack Multiple, from 11 to 02 o'clock, within 8 inches of joint: YES161.2 ft. CM - Crack Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES171.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start346 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish348.6 ft. AMH - Downstream Manhole, Survey Ends - 02 0335348.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (9)

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    47.9 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES

    51 ft. - Fracture Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    87.9 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES

    96.4 ft. - Crack Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES

  • Fracture Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES

    141.5 ft. - Fracture Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

    146.8 ft. - Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 11 to 02 o'clock, within 8 inches of joint: YES

    151.6 ft. - Crack Multiple, from 11 to 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES

    161.2 ft. - Crack Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    171.7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (16)

DistanceCodeObservation
96.4CM
0MWM
348.6AMH02 0335
141.5FC
348.6FM
47.9CM
146.8FM
346SSS
51FC
161.2CM
171.7FM
151.6CM
0MWL
0AMH02 0336
2SSS
87.9CL

Properties (7)

additional_info
SC411392
custom_field_three
MULTIPLE CRACKS/ MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2020-06-17T23:01:21-07:00
documentation
PROPIPE
is_lateral_inspection
false