Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 18, 2020, 06:47 AM
  • 02 0333_02 0332_06172020_235846.mp4

Date
06/17/2020
W/O
833634
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00259
PipeID
P02644
Time
11:47 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7733
Sewer Name
EAST COMPTON BOULEVARD RELIEF TRUNK
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
37
Purpose
Routine Assessment
Project
RFIR_WO_833634_TV02385_JUN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
18 in.
Upstream MH
02 0332
Downstream MH
02 0333
Dir. of Survey
Upstream
Length Surveyed
411 ft.
Total Length
411 ft.
Structural Index
3
Structural Quick
423O
Structural Rating
409
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
409
Pipe schematic from manhole 02 0332 to 02 0333
MH: 02 0332MH: 02 0333upstream0 ft. AMH - Upstream Manhole, Survey Ends - 02 03333 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish5.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish196.4 ft. FC - Fracture Circumferential, from 02 to 05 o'clock, within 8 inches of joint: YES260.3 ft. FM - Fracture Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES401.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start408.4 ft. FM - Fracture Multiple, from 09 to 10 o'clock, within 8 inches of joint: YES409 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start411 ft. AMH - Downstream Manhole, Survey Begins - 02 0332411 ft. MWM - Water Mark, 25 %of cross sectional area411 ft. MWL - Water Level, 20 %of cross sectional area

Observation photos (4)

  • Fracture Multiple, from 09 to 10 o'clock, within 8 inches of joint: YES

    2.6 ft. - Fracture Multiple, from 09 to 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    9.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES

    150.7 ft. - Fracture Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES

  • Fracture Circumferential, from 02 to 05 o'clock, within 8 inches of joint: YES

    214.6 ft. - Fracture Circumferential, from 02 to 05 o'clock, within 8 inches of joint: YES

Observations (11)

DistanceCodeObservation
0AMH02 0332
405.9CM
408SSS
0MWM
2.6FM
2SSS
150.7FM
214.6FC
0MWL
9.3CM
411AMH02 0333

Properties (7)

additional_info
SC411392
custom_field_three
MULTIPLE CRACKS/ SOME FRACTURE'S
custom_field_two
3
customer
1
datetime
2020-06-17T23:47:33-07:00
documentation
PROPIPE
is_lateral_inspection
false