Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 19, 2020, 06:24 AM
  • 02 0330_02 0329_06182020_233704.mp4

Date
06/18/2020
W/O
833634
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00259
PipeID
P02641
Time
11:24 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7733
Sewer Name
EAST COMPTON BOULEVARD RELIEF TRUNK
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
37
Purpose
Routine Assessment
Project
RFIR_WO_833634_TV02385_JUN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
18 in.
Upstream MH
02 0329
Downstream MH
02 0330
Dir. of Survey
Upstream
Length Surveyed
417.7 ft.
Total Length
417.7 ft.
Structural Index
3
Structural Quick
423O
Structural Rating
417
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
419
Pipe schematic from manhole 02 0329 to 02 0330
MH: 02 0329MH: 02 0330upstream0 ft. AMH - Upstream Manhole, Survey Ends - 02 03302.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish5.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish219.7 ft. FM - Fracture Multiple, from 11 to 05 o'clock, within 8 inches of joint: YES250.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"301.6 ft. FM - Fracture Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES363.3 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES363.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"412 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start415.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start417.7 ft. AMH - Downstream Manhole, Survey Begins - 02 0329417.7 ft. MWL - Water Level, 25 %of cross sectional area417.7 ft. MWM - Water Mark, 30 %of cross sectional area417.7 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (4)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 10 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES

    54.4 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES

  • Fracture Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES

    116.1 ft. - Fracture Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 11 to 05 o'clock, within 8 inches of joint: YES

    198 ft. - Fracture Multiple, from 11 to 05 o'clock, within 8 inches of joint: YES

Observations (14)

DistanceCodeObservation
2SSS
54.4DAGS
5.7CM
116.1FM
198FM
412.3CM
0AMH02 0329
54.4TFA
166.8TFA
0MWL
0MWM
415SSS
417.7AMH02 0330
0MGOCONNECTION AT MH 3 O'CLOCK

Properties (7)

additional_info
SC411392
custom_field_three
MULTIPLE CRACKS/SOME FRACTURE'S
custom_field_two
3
customer
1
datetime
2020-06-18T23:24:26-07:00
documentation
PROPIPE
is_lateral_inspection
false