Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 19, 2020, 04:13 AM
  • 02 0328_02 0327_06182020_212407.mp4

Date
06/18/2020
W/O
833634
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00259
PipeID
P02639
Time
9:13 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7734
Sewer Name
EAST COMPTON BOULEVARD RELIEF TRUNK
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
37
Purpose
Routine Assessment
Project
RFIR_WO_833634_TV02385_JUN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
18 in.
Upstream MH
02 0328
Downstream MH
02 0327
Dir. of Survey
Downstream
Length Surveyed
344.5 ft.
Total Length
344.5 ft.
Structural Index
3
Structural Quick
423L
Structural Rating
341
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
341
Pipe schematic from manhole 02 0328 to 02 0327
MH: 02 0328MH: 02 0327downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 03282 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES13.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start27.3 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES36.4 ft. FM - Fracture Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES339.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish342 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish344.5 ft. AMH - Downstream Manhole, Survey Ends - 02 0327

Observation photos (4)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    3.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    13.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES

    27.3 ft. - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES

    36.4 ft. - Fracture Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES

Observations (11)

DistanceCodeObservation
0MWL
36.4FM
0MWM
13.3CM
2SSS
342SSS
339.4CM
0AMH02 0328
344.5AMH02 0327
3.2FM
27.3FC

Properties (7)

additional_info
SC411393
custom_field_three
MULTIPLE CRACKS/SOME FRACTURE'S
custom_field_two
3
customer
1
datetime
2020-06-18T21:13:35-07:00
documentation
PROPIPE
is_lateral_inspection
false