Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 19, 2020, 04:24 AM
  • 02 0327_02 0326_06182020_214730.mp4

Date
06/18/2020
W/O
833634
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00259
PipeID
P02638
Time
9:24 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7734
Sewer Name
EAST COMPTON BOULEVARD RELIEF TRUNK
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
37
Purpose
Routine Assessment
Project
RFIR_WO_833634_TV02385_JUN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
18 in.
Upstream MH
02 0327
Downstream MH
02 0326
Dir. of Survey
Downstream
Length Surveyed
431.3 ft.
Total Length
431.3 ft.
Structural Index
3
Structural Quick
423P
Structural Rating
444
O&M Index
2
O&M Quick
2A00
O&M Rating
20
Overall Index
2
Overall Quick
Overall Rating
464
Pipe schematic from manhole 02 0327 to 02 0326
MH: 02 0327MH: 02 0326downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 03270 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start9.7 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES38.8 ft. CC - Crack Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES212.7 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES268.7 ft. FM - Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES278.4 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES382.6 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start415.7 ft. FM - Fracture Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES429 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish431.2 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Finish431.3 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE431.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish431.3 ft. AMH - Downstream Manhole, Survey Ends - 02 0326

Observation photos (8)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    9.7 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Crack Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES

    38.8 ft. - Crack Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES

  • Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES

    212.7 ft. - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

    268.7 ft. - Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

  • Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES

    278.4 ft. - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES

  • Deposits Settled Other,  10 %of cross sectional area, at 06 o'clock,  , within 8 inches of joint: YES, Start

    382.6 ft. - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES

    415.7 ft. - Fracture Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES

Observations (17)

DistanceCodeObservation
2CM
212.7FC
38.8CC
2SSS
431.3MGOCONN @ MH 9 O'CLOCK/ACTIVE
382.6DSZ
268.7FM
9.7CM
0MWL
278.4FC
431.3CM
429SSS
431.2DSZ
431.3AMH02 0326
0AMH02 0327
0MWM
415.7FM

Properties (7)

additional_info
SC411393
custom_field_three
MULTIPLE CRACKS/SOME FRACTURE'S
custom_field_two
3
customer
1
datetime
2020-06-18T21:24:56-07:00
documentation
PROPIPE
is_lateral_inspection
false