Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 19, 2020, 08:09 AM
  • 02 0325_02 0324_06192020_011848.mp4

Date
06/19/2020
W/O
833634
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00259
PipeID
P02636
Time
1:09 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7734
Sewer Name
EAST COMPTON BOULEVARD RELIEF TRUNK
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
37
Purpose
Routine Assessment
Project
RFIR_WO_833634_TV02385_JUN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
18 in.
Upstream MH
02 0325
Downstream MH
02 0324
Dir. of Survey
Downstream
Length Surveyed
367 ft.
Total Length
367 ft.
Structural Index
3
Structural Quick
443V
Structural Rating
367
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
367
Pipe schematic from manhole 02 0325 to 02 0324
MH: 02 0325MH: 02 0324downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 03250 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.6 ft. FM - Fracture Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES59.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES65.6 ft. FC - Fracture Circumferential, from 02 to 05 o'clock, within 8 inches of joint: YES79.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES100.8 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES126.6 ft. FM - Fracture Multiple, from 03 to 05 o'clock, within 8 inches of joint: YES136.5 ft. CM - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES146.2 ft. CS - Crack Spiral, from 07 to 09 o'clock, within 8 inches of joint: YES162.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start365 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish367 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish367 ft. AMH - Downstream Manhole, Survey Ends - 02 0324

Observation photos (9)

  • Fracture Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

    3.6 ft. - Fracture Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    59.5 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Circumferential, from 02 to 05 o'clock, within 8 inches of joint: YES

    65.6 ft. - Fracture Circumferential, from 02 to 05 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    79.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES

    100.8 ft. - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 03 to 05 o'clock, within 8 inches of joint: YES

    126.6 ft. - Fracture Multiple, from 03 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

    136.5 ft. - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 07 to 09 o'clock, within 8 inches of joint: YES

    146.2 ft. - Crack Spiral, from 07 to 09 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    162.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (16)

DistanceCodeObservation
0AMH02 0325
0MWM
365CM
59.5FM
367CM
65.6FC
100.8FC
0MWL
367AMH02 0324
136.5CM
146.2CS
2CM
79.6FM
3.6FM
162.1CM
126.6FM

Properties (7)

additional_info
SC411393
custom_field_three
MULTIPLE CRACKS/SOME FRACTURE'S
custom_field_two
3
customer
1
datetime
2020-06-19T01:09:01-07:00
documentation
PROPIPE
is_lateral_inspection
false