Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 4, 2020, 05:20 AM
  • 08 0158_08 0157_06032020_225049.mp4

Date
06/03/2020
W/O
833597
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00009
PipeID
P00215
Time
10:20 PM
Certificate
U-109-7948
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7320
Sewer Name
GRACE STREET TRUNK, SECTION 1
City
CARSON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Routine Assessment
Project
WO_833597_TV08146_JUN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
12 in.
Upstream MH
08 0158
Downstream MH
08 0157
Dir. of Survey
Downstream
Length Surveyed
321.5 ft.
Total Length
321.5 ft.
Structural Index
3
Structural Quick
4423
Structural Rating
22
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
22
Pipe schematic from manhole 08 0158 to 08 0157
MH: 08 0158MH: 08 0157downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 01586.3 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES14.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"49 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES55.9 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"57.7 ft. FC - Fracture Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES81 ft. FM - Fracture Multiple, from 11 to 02 o'clock, within 8 inches of joint: YES94 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"129.2 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"166.5 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES180.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"195.3 ft. FM - Fracture Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES207 ft. FM - Fracture Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES213.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"270.2 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"321.5 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK321.5 ft. AMH - Downstream Manhole, Survey Ends - 08 0157321.5 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (3)

  • Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES

    166.5 ft. - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES

    195.3 ft. - Fracture Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES

    207 ft. - Fracture Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES

Observations (20)

DistanceCodeObservation
195.3FM
321.5MGOCONNECTION AT MH 9 O'CLOCK
81FM
57.7FC
321.5AMH08 0157
6.3FC
321.5MGOCONNECTION AT MH 3 O'CLOCK
94TF
49FM
180.8TF
213.7TFC
55.9TFA
0MWM
166.5FC
129.2TF
0MWL
14.9TFC
207FM
270.2TF
0AMH08 0158

Properties (6)

additional_info
SC411309
custom_field_two
3
customer
1
datetime
2020-06-03T22:20:56-07:00
documentation
PRO PIPE
is_lateral_inspection
false