Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 11, 2020, 06:22 AM
  • 08 0187A_08 0187_06102020_233019.mp4

Date
06/10/2020
W/O
833557
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00009
PipeID
P00247
Time
11:22 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7725
Sewer Name
GRACE STREET TRUNK, SECTION 1
City
CARSON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Routine Assessment
Project
WO_833557_TV08019_JUN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
12 in.
Upstream MH
08 0187A
Downstream MH
08 0187
Dir. of Survey
Downstream
Length Surveyed
123 ft.
Total Length
123 ft.
Structural Index
3
Structural Quick
4A3B
Structural Rating
87
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
87
Pipe schematic from manhole 08 0187A to 08 0187
MH: 08 0187AMH: 08 0187downstream0 ft. AMH - Upstream Manhole, Survey Begins - 08 0187A0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWL - Water Level, 15 %of cross sectional area4.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start41.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"43 ft. FM - Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES44.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"69 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish69.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start89.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"91.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"122 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish123 ft. AMH - Downstream Manhole, Survey Ends - 08 0187

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

    43 ft. - Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

Observations (14)

DistanceCodeObservation
91.9TFC
123AMH08 0187
89.2TF
4.2CM
69.1FM
0AMH08 0187A
44.3TF
0MWM
122FM
0MGOCONNECTION AT MH 3 O'CLOCK
43FM
41.6TF
69CM
0MWL

Properties (7)

additional_info
SC411383
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2020-06-10T23:22:49-07:00
documentation
PROPIPE
is_lateral_inspection
false