Wastewater/Activity/PacpInspection/1.0Jun 11, 2020, 09:45 AM
  • 08 0184_08 0183_06112020_030118.mp4

Date
06/11/2020
W/O
833557
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00009
PipeID
P00243
Time
2:45 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7725
Sewer Name
GRACE STREET TRUNK, SECTION 1
City
CARSON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Routine Assessment
Project
WO_833557_TV08019_JUN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
12 in.
Upstream MH
08 0183
Downstream MH
08 0184
Dir. of Survey
Upstream
Length Surveyed
328.5 ft.
Total Length
328.5 ft.
Structural Index
3
Structural Quick
3K11
Structural Rating
187
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
191
Pipe schematic from manhole 08 0183 to 08 0184
MH: 08 0183MH: 08 0184upstream0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. AMH - Upstream Manhole, Survey Ends - 08 01842.5 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, at 08 o'clock, , within 8 inches of joint: YES3.5 ft. JSM - Joint Separated Medium75.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"78.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"125.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"128.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"172.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"175.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"222.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"224.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"244.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 05 o'clock, , within 8 inches of joint: YES272.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"275.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"307.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start320.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"322.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"328.5 ft. MWM - Water Mark, 25 %of cross sectional area328.5 ft. AMH - Downstream Manhole, Survey Begins - 08 0183328.5 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    21 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (22)

DistanceCodeObservation
84.2DAGS
250.3TF
21CM
328.5MGOCONNECTION AT MH 3 O'CLOCK
6TFC
328.5CM
105.9TF
8.3TF
155.9TF
328.5AMH08 0184
103.6TFC
0MWM
53.2TF
325JSM
202.8TFC
252.9TFC
153.3TFC
0AMH08 0183
0MWL
55.6TF
326DAGS
200.1TFC

Properties (7)

additional_info
SC411383
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2020-06-11T02:45:06-07:00
documentation
PROPIPE
is_lateral_inspection
false