Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 11, 2020, 08:36 AM
  • 08 0181_08 0180_06112020_015254.mp4

Date
06/11/2020
W/O
833557
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00009
PipeID
P00240
Time
1:36 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7725
Sewer Name
GRACE STREET TRUNK, SECTION 1
City
CARSON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Routine Assessment
Project
WO_833557_TV08019_JUN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
12 in.
Upstream MH
08 0181
Downstream MH
08 0180
Dir. of Survey
Downstream
Length Surveyed
374.4 ft.
Total Length
374.4 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 08 0181 to 08 0180
MH: 08 0181MH: 08 0180downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 018115.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"17.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"33.2 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES42.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start61.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"63.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"111 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"114.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"122.3 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"161.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"164.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"211.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"214.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"252 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"253.1 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"254 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"261.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"264.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"312.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"314.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"315 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"359.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"361.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"374.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish374.4 ft. AMH - Downstream Manhole, Survey Ends - 08 0180

Observation photos (7)

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    33.2 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    42.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    122.3 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    252 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    253.1 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    254 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    315 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

Observations (28)

DistanceCodeObservation
164.3TF
61.2TF
33.2CL
374.4CM
15.5TF
374.4AMH08 0180
0MWM
264.9TF
253.1TB
161.7TF
0MWL
42.4CM
361.6TFC
122.3TB
214.2TF
252TB
254TB
312.2TF
111TF
315TB
17.4TF
359.6TF
211.5TF
0AMH08 0181
114.9TF
314.9TF
261.5TF
63.6TFC

Properties (5)

additional_info
SC411383
customer
1
datetime
2020-06-11T01:36:25-07:00
documentation
PROPIPE
is_lateral_inspection
false