Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 24, 2020, 07:32 AM
  • 15 0869_15 0868_06242020_003919.mp4

Date
06/24/2020
W/O
833482
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00616
PipeID
P12662
Time
12:32 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7806
Sewer Name
15 MONROVIA OUTFALL TRUNK
City
MONROVIA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
05
Purpose
Routine Assessment
Project
WO_833482_TV15132_JUN2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
15 0869
Downstream MH
15 0868
Dir. of Survey
Downstream
Length Surveyed
36 ft.
Total Length
36 ft.
Structural Index
3
Structural Quick
3600
Structural Rating
18
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
18
Pipe schematic from manhole 15 0869 to 15 0868
MH: 15 0869MH: 15 0868downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 08690 ft. MGO - General Observation - CONNECTIONS IN MH, AT 3 AND 9 O' CLOCK0 ft. MWM - Water Mark, 45 %of cross sectional area3.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.4 ft. MGO - General Observation - MAG COATING ATTATCHED34.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish36 ft. MGO - General Observation - CONNECTION IN MH, 3 O' CLOCK36 ft. AMH - Downstream Manhole, Survey Ends - 15 0868

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.4 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
3.4SAP
36MGOCONNECTION IN MH, 3 O' CLOCK
36AMH15 0868
0MWL
0AMH15 0869
3.4MGOMAG COATING ATTATCHED
0MGOCONNECTIONS IN MH, AT 3 AND 9 O' CLOCK
34.2SAP
0MWM

Properties (7)

additional_info
SC411616
custom_field_three
AGGREGATE PROJECTING
custom_field_two
3
customer
1
datetime
2020-06-24T00:32:46-07:00
documentation
PROPIPE
is_lateral_inspection
false