Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 24, 2020, 07:40 AM
  • 15 0868_15 0732_06242020_010241.mp4

Date
06/24/2020
W/O
833482
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00616
PipeID
P12661
Time
12:40 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7806
Sewer Name
15 MONROVIA OUTFALL TRUNK
City
MONROVIA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
09
Purpose
Routine Assessment
Project
WO_833482_TV15132_JUN2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
15 0868
Downstream MH
15 0732
Dir. of Survey
Downstream
Length Surveyed
616.2 ft.
Total Length
616.2 ft.
Structural Index
3
Structural Quick
3W00
Structural Rating
360
O&M Index
2
O&M Quick
2T00
O&M Rating
214
Overall Index
3
Overall Quick
Overall Rating
574
Pipe schematic from manhole 15 0868 to 15 0732
MH: 15 0868MH: 15 0732downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 08680 ft. MGO - General Observation - CONNECTION IN MH, 3 O' CLOCK2.6 ft. MGO - General Observation - MAG COATING ATTATCHED14.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start83.8 ft. DSC - Deposits Settled Compacted, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start135.7 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 4"148.4 ft. TBI - Tap Break-In Intruding, at 01 o'clock, -, -, within 8 inches of joint: NO, 4", 1"285.7 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"614.1 ft. DSC - Deposits Settled Compacted, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish614.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish616.2 ft. AMH - Downstream Manhole, Survey Ends - 15 0732

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    14.3 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In Intruding, at 01 o'clock, -, -, within 8 inches of joint: NO, 4", 1"

    148.4 ft. - Tap Break-In Intruding, at 01 o'clock, -, -, within 8 inches of joint: NO, 4", 1"

Observations (13)

DistanceCodeObservation
0MWL
285.7TBA
0MWM
83.8DSC
614.3SAP
0AMH15 0868
14.3SAP
148.4TBI
135.7TB
2.6MGOMAG COATING ATTATCHED
0MGOCONNECTION IN MH, 3 O' CLOCK
614.1DSC
616.2AMH15 0732

Properties (7)

additional_info
SC411616
custom_field_three
AGGREGATE PROJECTING
custom_field_two
3
customer
1
datetime
2020-06-24T00:40:26-07:00
documentation
PROPIPE
is_lateral_inspection
false