Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 24, 2020, 05:45 AM
  • 15 0731_15 0730_06232020_230537.mp4

Date
06/23/2020
W/O
833482
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00616
PipeID
P12624
Time
10:45 PM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7806
Sewer Name
15 MONROVIA OUTFALL TRUNK
City
MONROVIA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
09
Purpose
Routine Assessment
Project
WO_833482_TV15132_JUN2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
15 0731
Downstream MH
15 0730
Dir. of Survey
Downstream
Length Surveyed
643.1 ft.
Total Length
643.1 ft.
Structural Index
3
Structural Quick
3Y00
Structural Rating
384
O&M Index
2
O&M Quick
2S00
O&M Rating
202
Overall Index
3
Overall Quick
Overall Rating
586
Pipe schematic from manhole 15 0731 to 15 0730
MH: 15 0731MH: 15 0730downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 07313.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.4 ft. MGO - General Observation - MAG COATING ATTATCHED135.4 ft. DSC - Deposits Settled Compacted, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start140.6 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 4"604.6 ft. TBB - Tap Break-In Abandoned, at 10 o'clock, -, within 8 inches of joint: NO, 4"641.9 ft. DSC - Deposits Settled Compacted, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish641.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish643.1 ft. AMH - Downstream Manhole, Survey Ends - 15 0730

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.4 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
643.1AMH15 0730
641.9DSC
135.4DSC
3.4SAP
604.6TBB
0MWL
140.6TB
3.4MGOMAG COATING ATTATCHED
0MWM
641.9SAP
0AMH15 0731

Properties (7)

additional_info
SC411616
custom_field_three
AGGREGATE PROJECTING
custom_field_two
3
customer
1
datetime
2020-06-23T22:45:03-07:00
documentation
PROPIPE
is_lateral_inspection
false