Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 16, 2020, 11:08 AM
  • B 1265_B 1264_7162020_044147.mp4

Date
07/16/2020
W/O
0833488
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z01126
PipeID
P25160
Time
4:08 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1484
Sewer Name
B JOINT OUTFALL B - UNIT 6J
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
12
Purpose
Maintenance Related
Project
20200716MDM_JOINT_OUTFALL_B_UNIT_6J
Material
NRCP
Shape
Circular
Height
18 in.
Upstream MH
B 1265
Downstream MH
B 1264
Dir. of Survey
Downstream
Length Surveyed
287.3 ft.
Total Length
287.3 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
3111
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
4
Pipe schematic from manhole B 1265 to B 1264
MH: B 1265MH: B 1264downstream0 ft. MGO - General Observation - MH CONN 9:00 ACTIVE0 ft. AMH - Upstream Manhole, Survey Begins - 4:40AM0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area8.2 ft. MGO - General Observation - 18" NRCP-CIPP156.7 ft. RFL - Roots Fine Lateral, from 02 to 03 o'clock - 1%156.7 ft. TBD - Tap Break-In Defective, at 02 o'clock, -, , within 8 inches of joint: NO, 6" - Open-25% ROOTS206.2 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - Open-NO ROOTS231.4 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - Open-APEARS FEW DEAD ROOTS287.3 ft. AMH - Downstream Manhole, Survey Ends - 5:00AM

Observation photos (5)

  • General Observation - 18" NRCP-CIPP

    8.2 ft. - General Observation - 18" NRCP-CIPP

  • Roots Fine Lateral, from 02 to 03 o'clock - 1%

    156.7 ft. - Roots Fine Lateral, from 02 to 03 o'clock - 1%

  • Tap Break-In Defective, at 02 o'clock, -,  , within 8 inches of joint: NO, 6" - Open-25% ROOTS

    156.7 ft. - Tap Break-In Defective, at 02 o'clock, -, , within 8 inches of joint: NO, 6" - Open-25% ROOTS

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - Open-NO ROOTS

    206.2 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - Open-NO ROOTS

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - Open-APEARS FEW DEAD ROOTS

    231.4 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - Open-APEARS FEW DEAD ROOTS

Observations (10)

DistanceCodeObservation
8.2MGO18" NRCP-CIPP
0MGOMH CONN 9:00 ACTIVE
287.3AMH5:00AM
231.4TBOpen-APEARS FEW DEAD ROOTS
0AMH4:40AM
156.7RFL1%
0MWM
156.7TBDOpen-25% ROOTS
206.2TBOpen-NO ROOTS
0MWL

Properties (6)

additional_info
EFFECTIVENESS OF CHEMICAL ROOT REMOVAL EVALUATION
customer
LACSD
datetime
2020-07-16T04:08:55-07:00
documentation
MARTIN,OLIVER 111,SHADLER,BARR
is_lateral_inspection
false
lining
CIPP