- Date
- 07/17/2020
- W/O
- 0833509
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z01125
- PipeID
- P13535
- Time
- 12:06 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- H1486
- Sewer Name
- B JOINT OUTFALL B - UNIT 6H
- City
- PASADENA
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 16
- Page No.
- 16
- Purpose
- Capital Improvement Program Assesment
- Project
- 20200717MDM_JOINT_OUTFALL_B_UNIT_6H
- Material
- NRCP
- Shape
- Circular
- Height
- 24 in.
- Upstream MH
- B 1215
- Downstream MH
- B 1214
- Dir. of Survey
- Downstream
- Length Surveyed
- 276.9 ft.
- Total Length
- 276.9 ft.
- Structural Index
- 2
- Structural Quick
- 3123
- Structural Rating
- 9
- O&M Index
- 2
- O&M Quick
- 2211
- O&M Rating
- 5
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 14
Pipe schematic from manhole B 1215 to B 1214 Observation photos (6)

2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

2 ft. - General Observation - MAG COAT 85% START

8 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

74.6 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

224.3 ft. - General Observation - 955 MAG COAT START

252.8 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE NO AGG