Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 4, 2020, 07:26 AM
  • B 0475A_B 0475_06042020_002909.mp4

Date
06/04/2020
W/O
833589
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00094
PipeID
P09000
Time
12:26 AM
Certificate
U-111-11880
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7686
Sewer Name
JOINT OUTFALL B - UNIT 5D
City
PASADENA
Loc. details
Alley
Location Code
H
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
06
Purpose
Routine Assessment
Project
RFIR_WO_833589_TV16037_JUN2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
57 in.
Upstream MH
B 0475A
Downstream MH
B 0475
Dir. of Survey
Downstream
Length Surveyed
11.2 ft.
Total Length
11.2 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
3
O&M Quick
4122
O&M Rating
8
Overall Index
3
Overall Quick
Overall Rating
14
Pipe schematic from manhole B 0475A to B 0475
MH: B 0475AMH: B 0475downstream0 ft. AMH - Upstream Manhole, Survey Begins - B 0475A0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 40 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start10.1 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish10.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish11.2 ft. AMH - Downstream Manhole, Survey Ends - B 0475

Observation photos (2)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
11.2AMHB 0475
2SAP
0AMHB 0475A
10.1SAP
2DAGS
0MWM
10.1DAGS
0MWL
0MGOCONNECTION AT MH 9 O'CLOCK

Properties (7)

additional_info
SC411278
custom_field_three
PROJECTING AGGREGATE
custom_field_two
3
customer
1
datetime
2020-06-04T00:26:01-07:00
documentation
PRO PIPE
is_lateral_inspection
false