- Date
- 06/03/2020
- W/O
- 833589
- Weather
- Dry
- Operator/Surveyor
- S. LOPEZ
- Sewer ID
- Z00094
- PipeID
- P08977
- Time
- 10:17 PM
- Certificate
- U-111-11880
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K7686
- Sewer Name
- JOINT OUTFALL B - UNIT 5D
- City
- PASADENA
- Loc. details
- Parking Lot
- Location Code
- G
- Use of Sewer
- Sanitary Sewer
- District
- District 16
- Page No.
- 11
- Purpose
- Routine Assessment
- Project
- RFIR_WO_833589_TV16037_JUN2020
- Sewer Type
- Gravity
- Material
- NRCP
- Shape
- Circular
- Height
- 18 in.
- Width
- 60 in.
- Upstream MH
- B 0463A
- Downstream MH
- B 0463
- Dir. of Survey
- Downstream
- Length Surveyed
- 219.8 ft.
- Total Length
- 219.8 ft.
- Structural Index
- 3
- Structural Quick
- 3H2G
- Structural Rating
- 212
- O&M Index
- 2
- O&M Quick
- 2H12
- O&M Rating
- 88
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 300
Pipe schematic from manhole B 0463A to B 0463 Observation photos (5)

2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

5.2 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

18.2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

138.7 ft. - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YESR, Start

219.8 ft. - General Observation - COCKROACHES IN MANHOLE