Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 4, 2020, 09:57 AM
  • B 0461_B 0460_06042020_030740.mp4

Date
06/04/2020
W/O
833589
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00094
PipeID
P08974
Time
2:57 AM
Certificate
U-111-11880
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7686
Sewer Name
JOINT OUTFALL B - UNIT 5D
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_833589_TV16037_JUN2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
60 in.
Upstream MH
B 0461
Downstream MH
B 0460
Dir. of Survey
Downstream
Length Surveyed
250.9 ft.
Total Length
250.9 ft.
Structural Index
3
Structural Quick
3I00
Structural Rating
147
O&M Index
2
O&M Quick
4131
O&M Rating
109
Overall Index
2
Overall Quick
Overall Rating
256
Pipe schematic from manhole B 0461 to B 0460
MH: B 0461MH: B 0460downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - B 04610 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start26.7 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"46.3 ft. RFJ - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YESR61.9 ft. RFJ - Roots Fine Joint, from 01 to 03 o'clock, within 8 inches of joint: YESR79.5 ft. RFJ - Roots Fine Joint, from 01 to 03 o'clock, within 8 inches of joint: YESR84.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"140.5 ft. RFJ - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YESR144.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"160 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"188.5 ft. RMJ - Roots Medium Joint, from 09 to 03 o'clock, 15 %, within 8 inches of joint: YESR210.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"248.9 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish248.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish250.9 ft. MGO - General Observation - COCKROACHES IN MANHOLE250.9 ft. AMH - Downstream Manhole, Survey Ends - B 0460

Observation photos (9)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YESR

    46.3 ft. - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YESR

  • Roots Fine Joint, from 01 to 03 o'clock, within 8 inches of joint: YESR

    61.9 ft. - Roots Fine Joint, from 01 to 03 o'clock, within 8 inches of joint: YESR

  • Roots Fine Joint, from 01 to 03 o'clock, within 8 inches of joint: YESR

    79.5 ft. - Roots Fine Joint, from 01 to 03 o'clock, within 8 inches of joint: YESR

  • Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YESR

    140.5 ft. - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YESR

  • Roots Medium Joint, from 09 to 03 o'clock, 15 %, within 8 inches of joint: YESR

    188.5 ft. - Roots Medium Joint, from 09 to 03 o'clock, 15 %, within 8 inches of joint: YESR

  • General Observation - COCKROACHES IN MANHOLE

    250.9 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (20)

DistanceCodeObservation
160TFA
0MGOCOCKROACHES IN MANHOLE
188.5RMJ
0AMHB 0461
0MWL
2DAGS
144.3TFC
248.9SAP
248.9DAGS
61.9RFJ
84.4TFC
250.9MGOCOCKROACHES IN MANHOLE
140.5RFJ
250.9AMHB 0460
26.7TBA
210.8TFA
2SAP
79.5RFJ
0MWM
46.3RFJ

Properties (7)

additional_info
SC411278
custom_field_three
PROJECTING AGGREGATE
custom_field_two
3
customer
1
datetime
2020-06-04T02:57:58-07:00
documentation
PRO PIPE
is_lateral_inspection
false