Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 3, 2020, 04:13 AM
  • 02 0810_02 0809_06022020_212910.mp4

Date
06/02/2020
W/O
833636
Weather
Dry
Operator/Surveyor
EN. RUIZ
Sewer ID
Z00294
PipeID
P03376
Time
9:13 PM
Certificate
U-116-07001919
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7757
Sewer Name
OLD RIVER SCHOOL ROAD TRUNK, SECTS 1&2
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
24
Purpose
Routine Assessment
Project
RFIR_WO_833636_TV02392_JUN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
18 in.
Upstream MH
02 0810
Downstream MH
02 0809
Dir. of Survey
Downstream
Length Surveyed
350.2 ft.
Total Length
350.2 ft.
Structural Index
4
Structural Quick
4734
Structural Rating
40
O&M Index
2
O&M Quick
2M00
O&M Rating
138
Overall Index
2
Overall Quick
Overall Rating
178
Pipe schematic from manhole 02 0810 to 02 0809
MH: 02 0810MH: 02 0809downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 08100 ft. MGO - General Observation - CONNECTION AT MH, 3 O'CLOCK0 ft. MGO - General Observation - COCKROACHES IN MH0 ft. MWM - Water Mark, 20 %of cross sectional area2.1 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, at 08 o'clock, , within 8 inches of joint: NO, Start5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"8.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"24 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES48.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"59.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"107.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"109 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: NO110.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"155.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"156 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES159 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"181 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES207.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"210.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"224.1 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES239.4 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES259.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"262.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"266.8 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES274 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES286 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES307.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"310.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"335.5 ft. FM - Fracture Multiple, from 07 to 03 o'clock, within 8 inches of joint: YES344 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES347.3 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, at 08 o'clock, , within 8 inches of joint: NO, Finish350.1 ft. MGO - General Observation - COCKROACHES IN MH350.2 ft. AMH - Downstream Manhole, Survey Ends - 02 0809

Observation photos (8)

  • General Observation - COCKROACHES IN MH

    0 ft. - General Observation - COCKROACHES IN MH

  • Deposits Attached Grease, 10 %of cross sectional area, at 08 o'clock,  , within 8 inches of joint: NO, Start

    2.1 ft. - Deposits Attached Grease, 10 %of cross sectional area, at 08 o'clock, , within 8 inches of joint: NO, Start

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    24 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    224.1 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    239.4 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    266.8 ft. - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 07 to 03 o'clock, within 8 inches of joint: YES

    335.5 ft. - Fracture Multiple, from 07 to 03 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MH

    350.1 ft. - General Observation - COCKROACHES IN MH

Observations (34)

DistanceCodeObservation
262.5TFC
0MWL
0AMH02 0810
310.9TFC
350.1MGOCOCKROACHES IN MH
159TFC
239.4FM
109FL
155.7TFC
8.3TFC
259.2TFC
24FM
0MGOCONNECTION AT MH, 3 O'CLOCK
48.2TFC
344FL
350.2AMH02 0809
347.3DAGS
156FM
224.1FM
0MGOCOCKROACHES IN MH
266.8FL
59.6TF
307.3TFC
207.4TFC
274FM
5TFC
110.7TFC
107.7TFC
335.5FM
0MWM
210.1TFC
286FM
2.1DAGS
181FL

Properties (7)

additional_info
SC411465
custom_field_three
FRACTURES, GREASE
custom_field_two
3
customer
1
datetime
2020-06-02T21:13:23-07:00
documentation
PRO PIPE
is_lateral_inspection
false