Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 2, 2020, 04:38 AM
  • 02 0804_02 0803_06012020_215655.mp4

Date
06/01/2020
W/O
833636
Weather
Dry
Operator/Surveyor
EN. RUIZ
Sewer ID
Z00294
PipeID
P03370
Time
9:38 PM
Certificate
U-116-07001919
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7756
Sewer Name
OLD RIVER SCHOOL ROAD TRUNK, SECTS 1&2
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
24
Purpose
Routine Assessment
Project
RFIR_WO_833636_TV02392_JUN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
18 in.
Upstream MH
02 0804
Downstream MH
02 0803
Dir. of Survey
Downstream
Length Surveyed
340.6 ft.
Total Length
340.6 ft.
Structural Index
4
Structural Quick
4D23
Structural Rating
102
O&M Index
2
O&M Quick
322M
O&M Rating
142
Overall Index
3
Overall Quick
Overall Rating
244
Pipe schematic from manhole 02 0804 to 02 0803
MH: 02 0804MH: 02 0803downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 08040 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start15 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish17.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES34.1 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 6"38.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"59.4 ft. FM - Fracture Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES74.5 ft. FM - Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES85 ft. RFB - Roots Fine Barrell, at 10 o'clock, within 8 inches of joint: NO85.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"88.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"108.4 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES134.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"138.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"181.5 ft. RMC - Roots Medium Connection, at 11 o'clock, 15 %, within 8 inches of joint: NO182.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"185.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES185.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"208.3 ft. FM - Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES220.6 ft. FM - Fracture Multiple, from 08 to 01 o'clock, within 8 inches of joint: YES232.6 ft. RML - Roots Medium Lateral, at 12 o'clock, 10 %, within 8 inches of joint: NO234 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"237.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"244.3 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES256.9 ft. FM - Fracture Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES274 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start281.1 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES283 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"285.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"308.2 ft. FM - Fracture Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES327.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"331.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"337 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish337.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Finish340.6 ft. AMH - Downstream Manhole, Survey Ends - 02 0803

Observation photos (14)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: NO, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    17.5 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

    59.4 ft. - Fracture Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

    74.5 ft. - Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    108.4 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Roots Medium Connection, at 11 o'clock, 15 %, within 8 inches of joint: NO

    181.5 ft. - Roots Medium Connection, at 11 o'clock, 15 %, within 8 inches of joint: NO

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    185.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

    208.3 ft. - Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 01 o'clock, within 8 inches of joint: YES

    220.6 ft. - Fracture Multiple, from 08 to 01 o'clock, within 8 inches of joint: YES

  • Roots Medium Lateral, at 12 o'clock, 10 %, within 8 inches of joint: NO

    232.6 ft. - Roots Medium Lateral, at 12 o'clock, 10 %, within 8 inches of joint: NO

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    244.3 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

    256.9 ft. - Fracture Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    281.1 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES

    308.2 ft. - Fracture Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES

Observations (38)

DistanceCodeObservation
327.9TFC
0MWL
283TFC
285.9TFC
185.1FM
181.5RMC
74.5FM
138.4TFC
185.7TFC
340.6AMH02 0803
208.3FM
134.2TFC
182.3TF
85RFB
220.6FM
244.3FM
337.5DAGS
232.6RML
108.4FM
88.7TFC
15SSS
274FM
256.9FM
331.3TFC
38.7TFC
0AMH02 0804
281.1FM
85.3TF
234TF
59.4FM
17.5FM
2.1DAGS
2SSS
308.2FM
0MWM
237.3TFC
34.1TF
337FM

Properties (7)

additional_info
SC411464
custom_field_three
CRACKS, FRACTURES, GREASE
custom_field_two
3
customer
1
datetime
2020-06-01T21:38:10-07:00
documentation
PRO PIPE
is_lateral_inspection
false