Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 2, 2020, 05:02 AM
  • 02 0803_02 0802_06012020_221817.mp4

Date
06/01/2020
W/O
833636
Weather
Dry
Operator/Surveyor
EN. RUIZ
Sewer ID
Z00294
PipeID
P03369
Time
10:02 PM
Certificate
U-116-07001919
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7756
Sewer Name
OLD RIVER SCHOOL ROAD TRUNK, SECTS 1&2
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
24
Purpose
Routine Assessment
Project
RFIR_WO_833636_TV02392_JUN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
18 in.
Upstream MH
02 0803
Downstream MH
02 0802
Dir. of Survey
Downstream
Length Surveyed
334.4 ft.
Total Length
334.4 ft.
Structural Index
3
Structural Quick
4931
Structural Rating
53
O&M Index
2
O&M Quick
2L11
O&M Rating
133
Overall Index
2
Overall Quick
Overall Rating
186
Pipe schematic from manhole 02 0803 to 02 0802
MH: 02 0803MH: 02 0802downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 08032.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start2.1 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start38 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish43.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"46 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"65.3 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES91.6 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"94.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"104 ft. FM - Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES144.3 ft. FM - Fracture Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES148.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"160.3 ft. RFC - Roots Fine Connection, at 02 o'clock160.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"162 ft. FM - Fracture Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES191.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"194.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"211 ft. FM - Fracture Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES235.1 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES245.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6" - CREACKED COVER248.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"267 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES270 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES277.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES294 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"297.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"316.8 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: NO330.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Finish334.4 ft. AMH - Downstream Manhole, Survey Ends - 02 0802

Observation photos (7)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: NO, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    65.3 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

    144.3 ft. - Fracture Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

  • Roots Fine Connection, at 02 o'clock

    160.3 ft. - Roots Fine Connection, at 02 o'clock

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    235.1 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    277.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: NO

    316.8 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: NO

Observations (31)

DistanceCodeObservation
334.4AMH02 0802
245.8TFCCREACKED COVER
2.1DAGS
94.6TFC
2.1SSS
211FM
46TFC
191.1TFC
160.3RFC
144.3FM
160.3TF
38SSS
65.3FM
267FL
194.4TFC
104FM
0MWM
148.9TFC
316.8FM
277.2FM
91.6TFC
270FM
43.3TFC
248.7TFC
297.3TFC
162FM
0MWL
330.4DAGS
294TFC
0AMH02 0803
235.1FM

Properties (7)

additional_info
SC411464
custom_field_three
CRACKS, FRACTURES, GREASE
custom_field_two
3
customer
1
datetime
2020-06-01T22:02:15-07:00
documentation
PRO PIPE
is_lateral_inspection
false