Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 2, 2020, 07:30 AM
  • 02 0797_02 0796_06022020_004136.mp4

Date
06/02/2020
W/O
833636
Weather
Dry
Operator/Surveyor
EN. RUIZ
Sewer ID
Z00294
PipeID
P03363
Time
12:30 AM
Certificate
U-116-07001919
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7756
Sewer Name
OLD RIVER SCHOOL ROAD TRUNK, SECTS 1&2
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
24
Purpose
Routine Assessment
Project
RFIR_WO_833636_TV02392_JUN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
21 in.
Upstream MH
02 0797
Downstream MH
02 0796
Dir. of Survey
Downstream
Length Surveyed
321.1 ft.
Total Length
321.1 ft.
Structural Index
4
Structural Quick
4H00
Structural Rating
172
O&M Index
2
O&M Quick
2L00
O&M Rating
126
Overall Index
3
Overall Quick
Overall Rating
298
Pipe schematic from manhole 02 0797 to 02 0796
MH: 02 0797MH: 02 0796downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 07970 ft. MGO - General Observation - COCKROACHES IN MH0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start14.1 ft. FM - Fracture Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES17.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"19.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"34.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start70.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"70.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"119.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"122 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"169 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"170 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"192.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish208.3 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES219.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"223.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6", 6"235.3 ft. FM - Fracture Multiple, from 08 to 01 o'clock, within 8 inches of joint: YES254.9 ft. FM - Fracture Multiple, from 11 to 02 o'clock, within 8 inches of joint: NO271.7 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"273.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"276 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start309.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"312 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"315 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish318.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Finish321.1 ft. AMH - Downstream Manhole, Survey Ends - 02 0796321.1 ft. MGO - General Observation - COCKROACHES IN MH

Observation photos (8)

  • General Observation - COCKROACHES IN MH

    0 ft. - General Observation - COCKROACHES IN MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: NO, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start

  • Fracture Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

    14.1 ft. - Fracture Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    34.7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    208.3 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 01 o'clock, within 8 inches of joint: YES

    235.3 ft. - Fracture Multiple, from 08 to 01 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 11 to 02 o'clock, within 8 inches of joint: NO

    254.9 ft. - Fracture Multiple, from 11 to 02 o'clock, within 8 inches of joint: NO

  • General Observation - COCKROACHES IN MH

    321.1 ft. - General Observation - COCKROACHES IN MH

Observations (30)

DistanceCodeObservation
169TFC
119.2TFC
312TFC
309.7TFC
219.3TFC
192.1FM
17.5TFC
321.1AMH02 0796
0AMH02 0797
315FM
254.9FM
0MGOCOCKROACHES IN MH
70.1TFC
34.7FM
273.2TFC
271.7TFC
70.3TF
170TFC
122TF
2.1DAGS
0MWM
208.3FM
19.8TF
223.9TFA
0MWL
235.3FM
276FM
14.1FM
321.1MGOCOCKROACHES IN MH
318.5DAGS

Properties (7)

additional_info
SC411464
custom_field_three
CRACKS, FRACTURES, GREASE
custom_field_two
3
customer
1
datetime
2020-06-02T00:30:00-07:00
documentation
PRO PIPE
is_lateral_inspection
false