Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 2, 2020, 07:54 AM
  • 02 0795A_02 0795_06022020_010649.mp4

Date
06/02/2020
W/O
833636
Weather
Dry
Operator/Surveyor
EN. RUIZ
Sewer ID
Z00294
PipeID
P03361
Time
12:54 AM
Certificate
U-116-07001919
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7756
Sewer Name
OLD RIVER SCHOOL ROAD TRUNK, SECTS 1&2
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
24
Purpose
Routine Assessment
Project
RFIR_WO_833636_TV02392_JUN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
21 in.
Upstream MH
02 0795A
Downstream MH
02 0795
Dir. of Survey
Downstream
Length Surveyed
214.7 ft.
Total Length
214.7 ft.
Structural Index
4
Structural Quick
4231
Structural Rating
11
O&M Index
2
O&M Quick
2G00
O&M Rating
82
Overall Index
2
Overall Quick
Overall Rating
93
Pipe schematic from manhole 02 0795A to 02 0795
MH: 02 0795AMH: 02 0795downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH, 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 02 0795A0 ft. MGO - General Observation - COCKROACHES IN MH2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start9.1 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"38.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"40.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"59.1 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"87.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"89.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"96.8 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES116.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"143 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"144.7 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES188.8 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"191.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6", 6"195.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES209.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Finish214.7 ft. AMH - Downstream Manhole, Survey Ends - 02 0795214.7 ft. MGO - General Observation - COCKROACHES IN MH

Observation photos (6)

  • General Observation - COCKROACHES IN MH

    0 ft. - General Observation - COCKROACHES IN MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: NO, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    96.8 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    144.7 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    195.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MH

    214.7 ft. - General Observation - COCKROACHES IN MH

Observations (22)

DistanceCodeObservation
116.1TFC
143TFC
0MWM
40.8TFC
144.7FM
0MWL
59.1TB
0MGOCONNECTION AT MH, 3 O'CLOCK
87.1TFC
188.8TFC
0AMH02 0795A
214.7AMH02 0795
2.1DAGS
38.4TFC
214.7MGOCOCKROACHES IN MH
0MGOCOCKROACHES IN MH
9.1TB
89.9TFC
195.6FM
209.5DAGS
191.1TFA
96.8CM

Properties (7)

additional_info
SC411464
custom_field_three
CRACKS, FRACTURES, GREASE
custom_field_two
3
customer
1
datetime
2020-06-02T00:54:36-07:00
documentation
PRO PIPE
is_lateral_inspection
false