Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 3, 2020, 05:22 AM
  • 02 0793_02 0792_06022020_223216.mp4

Date
06/02/2020
W/O
833636
Weather
Dry
Operator/Surveyor
EN. RUIZ
Sewer ID
Z00294
PipeID
P03357
Time
10:22 PM
Certificate
U-116-07001919
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7757
Sewer Name
OLD RIVER SCHOOL ROAD TRUNK, SECTS 1&2
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
24
Purpose
Routine Assessment
Project
RFIR_WO_833636_TV02392_JUN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
21 in.
Upstream MH
02 0793
Downstream MH
02 0792
Dir. of Survey
Downstream
Length Surveyed
332.9 ft.
Total Length
332.9 ft.
Structural Index
4
Structural Quick
4I00
Structural Rating
192
O&M Index
2
O&M Quick
2L00
O&M Rating
130
Overall Index
3
Overall Quick
Overall Rating
322
Pipe schematic from manhole 02 0793 to 02 0792
MH: 02 0793MH: 02 0792downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH, 3 O'CLOCK0 ft. MGO - General Observation - COCKROACHES IN MH0 ft. AMH - Upstream Manhole, Survey Begins - 02 07930 ft. MWL - Water Level, 15 %of cross sectional area2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start33.8 ft. FM - Fracture Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES36.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"57.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"79.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES100.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start102.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"105.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"153.1 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"156.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"201.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"204.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"252.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"255.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"306 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"308.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"328 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish328.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Finish332.9 ft. MGO - General Observation - COCKROACHES IN MH332.9 ft. AMH - Downstream Manhole, Survey Ends - 02 0792

Observation photos (6)

  • General Observation - COCKROACHES IN MH

    0 ft. - General Observation - COCKROACHES IN MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: NO, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start

  • Fracture Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES

    33.8 ft. - Fracture Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    79.3 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    100.3 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MH

    332.9 ft. - General Observation - COCKROACHES IN MH

Observations (25)

DistanceCodeObservation
332.9MGOCOCKROACHES IN MH
0MWM
57.4TFC
36.7TF
306TFC
102.4TFC
2.1DAGS
0MGOCONNECTION AT MH, 3 O'CLOCK
204.6TFC
201.2TFC
156.4TFC
100.3FM
0MGOCOCKROACHES IN MH
328.8DAGS
33.8FM
0AMH02 0793
308.9TF
153.1TFC
255.4TFC
0MWL
328FM
252.3TFC
332.9AMH02 0792
79.3FM
105.2TFC

Properties (7)

additional_info
SC411465
custom_field_three
FRACTURES, GREASE
custom_field_two
3
customer
1
datetime
2020-06-02T22:22:00-07:00
documentation
PRO PIPE
is_lateral_inspection
false