Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 3, 2020, 07:15 AM
  • 02 0783_02 0782_06032020_003040.mp4

Date
06/03/2020
W/O
833636
Weather
Dry
Operator/Surveyor
EN. RUIZ
Sewer ID
Z00294
PipeID
P03343
Time
12:15 AM
Certificate
U-116-07001919
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7757
Sewer Name
OLD RIVER SCHOOL ROAD TRUNK, SECTS 1&2
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
27
Purpose
Routine Assessment
Project
RFIR_WO_833636_TV02392_JUN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
24 in.
Upstream MH
02 0783
Downstream MH
02 0782
Dir. of Survey
Downstream
Length Surveyed
336.7 ft.
Total Length
336.7 ft.
Structural Index
4
Structural Quick
4E32
Structural Rating
126
O&M Index
2
O&M Quick
2L00
O&M Rating
132
Overall Index
3
Overall Quick
Overall Rating
258
Pipe schematic from manhole 02 0783 to 02 0782
MH: 02 0783MH: 02 0782downstream0 ft. MGO - General Observation - COCKROACHES IN MH0 ft. AMH - Upstream Manhole, Survey Begins - 02 07830 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start4.6 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: NO25.7 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES37.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES44.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"61.7 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES70.2 ft. FM - Fracture Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES82.5 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES95.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"146 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 6"147.8 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6"160 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start194.1 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"245 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"285.6 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish300.5 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES327.6 ft. FM - Fracture Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES333.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Finish336.7 ft. MGO - General Observation - COCKROACHES IN MH336.7 ft. AMH - Downstream Manhole, Survey Ends - 02 0782

Observation photos (11)

  • General Observation - COCKROACHES IN MH

    0 ft. - General Observation - COCKROACHES IN MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: NO, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: NO

    4.6 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: NO

  • Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    25.7 ft. - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    37.7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    61.7 ft. - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    82.5 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    160 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    300.5 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES

    327.6 ft. - Fracture Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MH

    336.7 ft. - General Observation - COCKROACHES IN MH

Observations (24)

DistanceCodeObservation
285.6FM
82.5FM
245TFC
0MGOCOCKROACHES IN MH
146TF
2.1DAGS
0AMH02 0783
37.7FM
147.8TB
336.7MGOCOCKROACHES IN MH
95.1TFC
160FM
25.7FL
61.7FL
333.8DAGS
70.2FM
327.6FM
300.5FM
0MWM
336.7AMH02 0782
4.6FM
194.1TF
0MWL
44.7TFC

Properties (7)

additional_info
SC411465
custom_field_three
FRACTURES, GREASE
custom_field_two
3
customer
1
datetime
2020-06-03T00:15:04-07:00
documentation
PRO PIPE
is_lateral_inspection
false