Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 3, 2020, 08:05 AM
  • 02 0781_02 0780_06032020_011519.mp4

Date
06/03/2020
W/O
833636
Weather
Dry
Operator/Surveyor
EN. RUIZ
Sewer ID
Z00294
PipeID
P03341
Time
1:05 AM
Certificate
U-116-07001919
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7757
Sewer Name
OLD RIVER SCHOOL ROAD TRUNK, SECTS 1&2
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
24
Purpose
Routine Assessment
Project
RFIR_WO_833636_TV02392_JUN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
24 in.
Upstream MH
02 0781
Downstream MH
02 0780
Dir. of Survey
Downstream
Length Surveyed
297.2 ft.
Total Length
297.2 ft.
Structural Index
4
Structural Quick
4C00
Structural Rating
80
O&M Index
2
O&M Quick
2K00
O&M Rating
116
Overall Index
3
Overall Quick
Overall Rating
196
Pipe schematic from manhole 02 0781 to 02 0780
MH: 02 0781MH: 02 0780downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 07810 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start14.3 ft. FM - Fracture Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES36.1 ft. FM - Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES36.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"88.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"95.5 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES134.2 ft. FM - Fracture Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES135 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"139.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start188.5 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"210.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish217.7 ft. FM - Fracture Multiple, from 07 to 04 o'clock, within 8 inches of joint: NO229 ft. FM - Fracture Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES263.4 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"292.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Finish297.2 ft. AMH - Downstream Manhole, Survey Ends - 02 0780

Observation photos (8)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: NO, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start

  • Fracture Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES

    14.3 ft. - Fracture Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

    36.1 ft. - Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    95.5 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES

    134.2 ft. - Fracture Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    139.3 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 07 to 04 o'clock, within 8 inches of joint: NO

    217.7 ft. - Fracture Multiple, from 07 to 04 o'clock, within 8 inches of joint: NO

  • Fracture Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES

    229 ft. - Fracture Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES

Observations (19)

DistanceCodeObservation
36.1FM
36.2TFC
0AMH02 0781
217.7FM
139.3FM
188.5TFC
297.2AMH02 0780
263.4TF
14.3FM
2.1DAGS
292.9DAGS
229FM
0MWM
0MWL
95.5FM
88.3TFC
210.2FM
134.2FM
135TFC

Properties (7)

additional_info
SC411465
custom_field_three
FRACTURES, GREASE
custom_field_two
3
customer
1
datetime
2020-06-03T01:05:00-07:00
documentation
PRO PIPE
is_lateral_inspection
false