Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 4, 2020, 04:19 AM
  • 02 0750_02 0749A_06032020_213110.mp4

Date
06/03/2020
W/O
833636
Weather
Dry
Operator/Surveyor
EN. RUIZ
Sewer ID
Z00294
PipeID
P03307
Time
9:19 PM
Certificate
U-116-07001919
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7758
Sewer Name
OLD RIVER SCHOOL ROAD TRUNK, SECTS 1&2
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
26
Purpose
Routine Assessment
Project
RFIR_WO_833636_TV02392_JUN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 0750
Downstream MH
02 0749A
Dir. of Survey
Downstream
Length Surveyed
193.7 ft.
Total Length
193.7 ft.
Structural Index
3
Structural Quick
4132
Structural Rating
10
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole 02 0750 to 02 0749A
MH: 02 0750MH: 02 0749Adownstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 07500 ft. MGO - General Observation - COCKROACHES IN MH0 ft. MWM - Water Mark, 15 %of cross sectional area10.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"13.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"35.5 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES43.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"45.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"85.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"91.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"117.2 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES130.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"154.2 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"185.8 ft. FS - Fracture Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES190.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"193.4 ft. MGO - General Observation - CONNECTION AT MH, 3 O'CLOCK193.4 ft. MGO - General Observation - COCKROACHES IN MH193.7 ft. AMH - Downstream Manhole, Survey Ends - 02 0749A

Observation photos (5)

  • General Observation - COCKROACHES IN MH

    0 ft. - General Observation - COCKROACHES IN MH

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    35.5 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    117.2 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES

    185.8 ft. - Fracture Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MH

    193.4 ft. - General Observation - COCKROACHES IN MH

Observations (19)

DistanceCodeObservation
0MWL
43.9TFC
91.9TFC
193.4MGOCONNECTION AT MH, 3 O'CLOCK
0AMH02 0750
45.5TF
0MGOCOCKROACHES IN MH
13.7TFC
130.1TF
190.3TF
193.7AMH02 0749A
35.5CM
154.2TB
10.4TF
0MWM
193.4MGOCOCKROACHES IN MH
85.6TFC
117.2FM
185.8FS

Properties (7)

additional_info
SC411466
custom_field_three
CRACK, FRACTURES
custom_field_two
3
customer
1
datetime
2020-06-03T21:19:29-07:00
documentation
PRO PIPE
is_lateral_inspection
false