Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 24, 2020, 05:11 AM
  • 14 0453_14 0452_06232020_223121.mp4

Date
06/23/2020
W/O
833635
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00570
PipeID
P18541
Time
10:11 PM
Certificate
U-111-11880
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7859
Sewer Name
AVENUE "I" TRUNK
City
LANCASTER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_833635_TV14079_JUN2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
14 0453
Downstream MH
14 0452
Dir. of Survey
Downstream
Length Surveyed
390.2 ft.
Total Length
390.2 ft.
Structural Index
3
Structural Quick
3N00
Structural Rating
228
O&M Index
2
O&M Quick
2N00
O&M Rating
154
Overall Index
3
Overall Quick
Overall Rating
382
Pipe schematic from manhole 14 0453 to 14 0452
MH: 14 0453MH: 14 0452downstream0 ft. AMH - Upstream Manhole, Survey Begins - 14 04530 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - CONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start6.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start61.4 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"110.5 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"113.2 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"161.6 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"164.6 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"212.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"216.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"263.7 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"267.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"311.4 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"314.5 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"362.5 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"365.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"387.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish387.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish390.2 ft. AMH - Downstream Manhole, Survey Ends - 14 0452

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (23)

DistanceCodeObservation
311.4TFC
365.9TFA
212.9TF
314.5TFA
387.3DAGS
0AMH14 0453
110.5TFA
267.2TFC
263.7TFC
161.6TF
0MWL
164.6TFA
216.2TFC
0MGOCONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK
390.2AMH14 0452
61.4TFC
0MWM
2DAGS
6.9CM
113.2TFC
362.5TFC
387.3CM
0MGOCOCKROACHES IN MANHOLE

Properties (7)

additional_info
SC411300
custom_field_three
MULTIPLE CRACKS THROUGHOUT
custom_field_two
2
customer
1
datetime
2020-06-23T22:11:29-07:00
documentation
PRO PIPE
is_lateral_inspection
false