Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 27, 2020, 08:38 AM
  • 21 1141_21 1140 _05272020_014252.mp4

Date
05/27/2020
W/O
828935
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00780
PipeID
P16235
Time
1:38 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7673
Sewer Name
21 POMONA BOULEVARD INTERCEPTOR TRUNK
City
POMONA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
15
Purpose
Routine Assessment
Project
RFIR_WO_828935_TV21064_MAY2020
Sewer Type
Siphon
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
33 in.
Upstream MH
21 1140
Downstream MH
21 1141
Dir. of Survey
Upstream
Length Surveyed
2 ft.
Total Length
2 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
11
Pipe schematic from manhole 21 1140 to 21 1141
MH: 21 1140MH: 21 1141upstream0 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES0 ft. MSA - Survey Abandoned - VIEW OF UPLEG OF D/S SIPHON.0 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES2 ft. MWL - Water Level, 30 %of cross sectional area2 ft. MWM - Water Mark, 50 %of cross sectional area2 ft. AMH - Downstream Manhole, Survey Begins - 21 1140

Observation photos (4)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Survey Abandoned - VIEW OF UPLEG OF D/S SIPHON.

    2 ft. - Survey Abandoned - VIEW OF UPLEG OF D/S SIPHON.

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES

Observations (7)

DistanceCodeObservation
2SAP
2MSAVIEW OF UPLEG OF D/S SIPHON.
2SSS
0MWL
0MWM
2DAGS
0AMH21 1140

Properties (7)

additional_info
SC411265
custom_field_two
3
customer
LACSD
datetime
2020-05-27T01:38:59-07:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
31044