Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 29, 2020, 05:23 AM
  • 18 0366_18 0365 _05282020_222856.mp4

Date
05/28/2020
W/O
828939
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00714
PipeID
P14200
Time
10:23 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7714
Sewer Name
18 WASHINGTON BOULEVARD TRUNK
City
WHITTIER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
09
Purpose
Routine Assessment
Project
RFIR_WO_828939_TV18179_MAY2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
18 0366
Downstream MH
18 0365
Dir. of Survey
Downstream
Length Surveyed
41.3 ft.
Total Length
41.3 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
7
Pipe schematic from manhole 18 0366 to 18 0365
MH: 18 0366MH: 18 0365downstream0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 03660 ft. MWL - Water Level, 40 %of cross sectional area2.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start41.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish41.2 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK CAPPED41.3 ft. AMH - Downstream Manhole, Survey Ends - 18 036541.3 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK CAPPED

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
0MGOCONNECTION AT MH 3 O'CLOCK
41.2CM
41.2MGOCONNECTION AT MH 9 O'CLOCK CAPPED
41.3AMH18 0365
2.1CM
41.3MGOCONNECTION AT MH 3 O'CLOCK CAPPED
0MWM
0AMH18 0366
0MWL

Properties (6)

additional_info
SC411371
custom_field_two
2
customer
LACSD
datetime
2020-05-28T22:23:51-07:00
documentation
PROPIPE
is_lateral_inspection
false