Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 14, 2020, 05:12 AM
  • 15 0060_15 0059A_05132020_222150.mp4

Date
05/13/2020
W/O
828936
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00622
PipeID
P11954
Time
10:12 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7663
Sewer Name
15 PUENTE TRUNK
City
CITY OF INDUSTRY
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
35
Purpose
Routine Assessment
Project
RFIR_WO_828936_TV15220_MAY2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
15 0060
Downstream MH
15 0059A
Dir. of Survey
Downstream
Length Surveyed
12.6 ft.
Total Length
12.6 ft.
Structural Index
4
Structural Quick
4200
Structural Rating
8
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
12
Pipe schematic from manhole 15 0060 to 15 0059A
MH: 15 0060MH: 15 0059Adownstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 00600 ft. MWM - Water Mark, 10 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start4 ft. FM - Fracture Multiple, from 06 to 08 o'clock, within 8 inches of joint: YES10.1 ft. FM - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES10.2 ft. MGP - General Photograph - MULTIPLE FRACTURES11.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish12.6 ft. AMH - Downstream Manhole, Survey Ends - 15 0059A

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Multiple, from 06 to 08 o'clock, within 8 inches of joint: YES

    4 ft. - Fracture Multiple, from 06 to 08 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

    10.1 ft. - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

  • General Photograph - MULTIPLE FRACTURES

    10.2 ft. - General Photograph - MULTIPLE FRACTURES

Observations (9)

DistanceCodeObservation
10.1FM
2DAGS
4FM
0MWL
0AMH15 0060
12.6AMH15 0059A
11.2DAGS
10.2MGPMULTIPLE FRACTURES
0MWM

Properties (6)

additional_info
SC411254
custom_field_two
2
customer
LACSD
datetime
2020-05-13T22:12:59-07:00
documentation
PRO PIPE
is_lateral_inspection
false