Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 7, 2020, 07:58 AM
  • 08 0507_08 0506_772020_014829.mp4

Date
07/07/2020
W/O
0828883
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00021
PipeID
P00568
Time
12:58 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1468
Sewer Name
08 VICTORIA STREET TRUNK
City
COMPTON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
04
Purpose
Capital Improvement Program Assesment
Project
202007MDM_VICTORIA_STREET_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
08 0507
Downstream MH
08 0506
Dir. of Survey
Downstream
Length Surveyed
323.6 ft.
Total Length
323.6 ft.
Structural Index
2
Structural Quick
362B
Structural Rating
50
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
50
Pipe schematic from manhole 08 0507 to 08 0506
MH: 08 0507MH: 08 0506downstream0 ft. MGO - General Observation - MH CONN 6:00 ACTIVE0 ft. MGO - General Observation - MH CONN 9:00 ACTIVE0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:55AM0 ft. MWM - Water Mark, 40 %of cross sectional area8 ft. MGO - General Observation - 15" VCP57 ft. TFB - Tap Factory Made Abandoned, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped59.9 ft. FC - Fracture Circumferential, from 07 to 08 o'clock, within 8 inches of joint: YES - HAIRLINE60 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped77.2 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SLIGHT108.2 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped110.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H111.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped123.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT123.3 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - HAIRLINE125.2 ft. FC - Fracture Circumferential, from 11 to 12 o'clock, within 8 inches of joint: NO - HAIRLINE127.9 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL128 ft. FC - Fracture Circumferential, from 12 to 01 o'clock, within 8 inches of joint: YES - H129.6 ft. FC - Fracture Circumferential, from 11 to 12 o'clock, within 8 inches of joint: YES - H130.9 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - H133.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - SLIGHT158.6 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H159.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped162.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped165.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SL171.3 ft. MWM - Water Mark, 20 %of cross sectional area189.9 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - H200.2 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - H206.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped209 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped215.9 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - SL227.3 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - SL230.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT241.9 ft. MGO - General Observation - LONG SLIGHT FRACTURE246 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - SL251 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - H257.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped259.1 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - H260.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped267.1 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H274.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - SL308.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Capped311.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H313.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped323.3 ft. MGO - General Observation - MH CONN 3:00 ACTIVE323.6 ft. AMH - Downstream Manhole, Survey Ends - 2:45AM

Observation photos (4)

  • General Observation - 15" VCP

    8 ft. - General Observation - 15" VCP

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

    123.1 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

    230.9 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

  • General Observation - LONG SLIGHT FRACTURE

    241.9 ft. - General Observation - LONG SLIGHT FRACTURE

Observations (46)

DistanceCodeObservation
0MGOMH CONN 6:00 ACTIVE
133.7FLSLIGHT
0MGOMH CONN 9:00 ACTIVE
227.3FCSL
323.3MGOMH CONN 3:00 ACTIVE
260.2TFCCapped
251FCH
241.9MGOLONG SLIGHT FRACTURE
128FCH
215.9FCSL
8MGO15" VCP
259.1FCH
159.8TFCCapped
313.3TFCCapped
162.8TFCCapped
158.6FCH
77.2FCSLIGHT
230.9FLSLIGHT
127.9FCSL
0MWL
206.9TFCCapped
189.9FCH
57TFBCapped
308.2TFCCapped
171.3MWM
59.9FCHAIRLINE
274.3FLSL
108.2TFCCapped
0AMH1:55AM
257.3TFCCapped
323.6AMH2:45AM
111.7TFCCapped
130.9FCH
165.2FLSL
209TFCCapped
246FCSL
0MWM
110.5FLH
125.2FCHAIRLINE
123.1FLSLIGHT
129.6FCH
60TFCCapped
267.1FCH
311.2FLH
123.3FCHAIRLINE
200.2FLH

Properties (6)

custom_field_three
SLIGHT LONG FRACTURE JOINT TO JOINT LONGER
custom_field_two
2
customer
LACSD
datetime
2020-07-07T00:58:35-07:00
documentation
MARTIN,OLIVER 111,SHADLER,BARR
is_lateral_inspection
false