Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 28, 2020, 09:49 AM
  • 18 0451_18 0450 _05282020_030857.mp4

Date
05/28/2020
W/O
828932
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00675
PipeID
P14302
Time
2:49 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7712
Sewer Name
18 FLORENCE AVENUE TRUNK
City
SANTA FE SPRINGS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
20
Purpose
Routine Assessment
Project
RFIR_WO_828932_TV18097_MAY2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0450
Downstream MH
18 0451
Dir. of Survey
Upstream
Length Surveyed
320.5 ft.
Total Length
320.5 ft.
Structural Index
3
Structural Quick
3L00
Structural Rating
189
O&M Index
2
O&M Quick
2K00
O&M Rating
122
Overall Index
3
Overall Quick
Overall Rating
311
Pipe schematic from manhole 18 0450 to 18 0451
MH: 18 0450MH: 18 0451upstream0 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish0 ft. MGO - General Observation - CONNECTION AT MH, 12 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Ends - 18 04510 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish58.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"84.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"110.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"131.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"157.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"183.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"209.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"235 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"260.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"286.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"305.8 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start306.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"316.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start320.5 ft. MWL - Water Level, 20 %of cross sectional area320.5 ft. MWM - Water Mark, 25 %of cross sectional area320.5 ft. AMH - Downstream Manhole, Survey Begins - 18 0450

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    14.7 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

Observations (20)

DistanceCodeObservation
137.3TFC
0MWL
0MWM
14.7DAE
189.3TFC
85.5TFC
4.2CM
320.5DAE
320.5MGOCONNECTION AT MH, 12 O'CLOCK
163.3TFC
261.7TFC
111.4TFC
14.2TFC
235.6TFC
320.5AMH18 0451
320.5CM
0AMH18 0450
210.1TFC
60.1TFC
34TFC

Properties (6)

additional_info
SC411369
custom_field_two
3
customer
LACSD
datetime
2020-05-28T02:49:51-07:00
documentation
PROPIPE
is_lateral_inspection
false