Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 29, 2020, 05:57 AM
  • 29 0003_29 0002_05282020_231211.mp4

Date
05/28/2020
W/O
828931
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00849
PipeID
P17677
Time
10:57 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7677
Sewer Name
29 SIGNAL HILL OUTFALL TRUNK
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
19
Purpose
Routine Assessment
Project
RFIR_WO_828931_TV29096_MAY2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
29 0003
Downstream MH
29 0002
Dir. of Survey
Downstream
Length Surveyed
334.1 ft.
Total Length
334.1 ft.
Structural Index
4
Structural Quick
5I3L
Structural Rating
445
O&M Index
2
O&M Quick
312L
O&M Rating
135
Overall Index
3
Overall Quick
Overall Rating
580
Pipe schematic from manhole 29 0003 to 29 0002
MH: 29 0003MH: 29 0002downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 29 00030 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. MGO - General Observation - MAG COATING THROUGHOUT10.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start16.7 ft. ID - Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES84.4 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start333.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish333.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish333.2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish334.1 ft. AMH - Downstream Manhole, Survey Ends - 29 0002

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - MAG COATING THROUGHOUT

    2 ft. - General Observation - MAG COATING THROUGHOUT

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    10.7 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES

    16.7 ft. - Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    84.4 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
2DAGS
334.1AMH29 0002
333.2DAGS
2MGOMAG COATING THROUGHOUT
0MWL
333.2SAP
16.7ID
333.2SRV
10.7SAP
84.4SRV
0AMH29 0003
0MWM

Properties (6)

additional_info
SC411269
custom_field_two
2
customer
LACSD
datetime
2020-05-28T22:57:47-07:00
documentation
PRO PIPE
is_lateral_inspection
false