Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 13, 2020, 07:41 AM
  • 15 0186_15 0185 _05132020_004909.mp4

Date
05/13/2020
W/O
829157
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00605
PipeID
P12110
Time
12:41 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7660
Sewer Name
15 FERRIS ROAD TRUNK
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
23
Purpose
Routine Assessment
Project
RFIR_WO_829157_TV15249_MAY2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
15 0186
Downstream MH
15 0185
Dir. of Survey
Downstream
Length Surveyed
77.8 ft.
Total Length
77.8 ft.
Structural Index
3
Structural Quick
3B00
Structural Rating
42
O&M Index
2
O&M Quick
2B00
O&M Rating
30
Overall Index
2
Overall Quick
Overall Rating
72
Pipe schematic from manhole 15 0186 to 15 0185
MH: 15 0186MH: 15 0185downstream0 ft. AMH - Upstream Manhole, Survey Begins - 15 01860 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start8.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start37.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"56.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"76.8 ft. RPZ - Repair Other, within 8 inches of joint: YES - LINK PIPE77.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish77.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish77.8 ft. MSA - Survey Abandoned - LINK PIPE DAMAGED

Observation photos (5)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    8.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Repair Other, within 8 inches of joint: YES - LINK PIPE

    76.8 ft. - Repair Other, within 8 inches of joint: YES - LINK PIPE

  • Survey Abandoned - LINK PIPE DAMAGED

    77.8 ft. - Survey Abandoned - LINK PIPE DAMAGED

Observations (12)

DistanceCodeObservation
0AMH15 0186
77.8DAGS
0MWM
37.9TFA
56.7TFA
77.8CM
76.8RPZLINK PIPE
2DAGS
0MWL
8.2CM
77.8MSALINK PIPE DAMAGED
0MGOCOCKROACHES IN MANHOLE

Properties (6)

additional_info
SC411251
custom_field_two
3
customer
LACSD
datetime
2020-05-13T00:41:10-07:00
documentation
PRO PIPE
is_lateral_inspection
false