Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 14, 2020, 08:30 AM
  • 01 0958_01 0957_05142020_013909.mp4

Date
05/14/2020
W/O
828917
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00228
PipeID
P01795
Time
1:30 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7664
Sewer Name
01 WRIGHT ROAD TRUNK
City
BELL
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_828917_TV01251_MAY2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
01 0958
Downstream MH
01 0957
Dir. of Survey
Downstream
Length Surveyed
300.1 ft.
Total Length
300.1 ft.
Structural Index
2
Structural Quick
392C
Structural Rating
65
O&M Index
2
O&M Quick
2K00
O&M Rating
118
Overall Index
2
Overall Quick
Overall Rating
183
Pipe schematic from manhole 01 0958 to 01 0957
MH: 01 0958MH: 01 0957downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 09580 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWM - Water Mark, 40 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start157.6 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start254.9 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish254.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start298.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish298.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish300.1 ft. AMH - Downstream Manhole, Survey Ends - 01 0957

Observation photos (4)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    157.6 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    254.9 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
0MWL
298.7DAGS
254.9CL
2DAGS
298.7FL
0AMH01 0958
157.6CL
0MGOCOCKROACHES IN MANHOLE
300.1AMH01 0957
0MWM
254.9FL

Properties (7)

additional_info
SC411255
custom_field_two
2
customer
LACSD
datetime
2020-05-14T01:30:43-07:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
10286