Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 15, 2020, 05:46 AM
  • 01 0956_01 0955_05142020_225256.mp4

Date
05/14/2020
W/O
828917
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00228
PipeID
P01793
Time
10:46 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7665
Sewer Name
01 WRIGHT ROAD TRUNK
City
BELL
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_828917_TV01251_MAY2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
01 0956
Downstream MH
01 0955
Dir. of Survey
Downstream
Length Surveyed
41 ft.
Total Length
41 ft.
Structural Index
2
Structural Quick
2300
Structural Rating
6
O&M Index
2
O&M Quick
4128
O&M Rating
20
Overall Index
2
Overall Quick
Overall Rating
26
Pipe schematic from manhole 01 0956 to 01 0955
MH: 01 0956MH: 01 0955downstream0 ft. MWL - Water Level, 40 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MH0 ft. MGO - General Observation - CONNECTION AT MH, 3 AND 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 01 09560 ft. MWM - Water Mark, 50 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start23.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start39.9 ft. MGO - General Observation - COCKROACHES IN MH39.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish39.9 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish41 ft. AMH - Downstream Manhole, Survey Ends - 01 0955

Observation photos (4)

  • General Observation - COCKROACHES IN MH

    0 ft. - General Observation - COCKROACHES IN MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    23.8 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MH

    39.9 ft. - General Observation - COCKROACHES IN MH

Observations (11)

DistanceCodeObservation
41AMH01 0955
0MWL
39.9MGOCOCKROACHES IN MH
23.8CL
0MGOCOCKROACHES IN MH
0MGOCONNECTION AT MH, 3 AND 9 O'CLOCK
39.9DAGS
2DAGS
0AMH01 0956
39.9CL
0MWM

Properties (7)

additional_info
SC411256
custom_field_two
3
customer
LACSD
datetime
2020-05-14T22:46:25-07:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
10286