Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 18, 2020, 09:10 AM
  • 01 0946_01 0945_05182020_022113.mp4

Date
05/18/2020
W/O
828917
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00228
PipeID
P01783
Time
2:10 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7666
Sewer Name
01 WRIGHT ROAD TRUNK
City
CUDAHY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_828917_TV01251_MAY2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
01 0946
Downstream MH
01 0945
Dir. of Survey
Downstream
Length Surveyed
292.1 ft.
Total Length
292.1 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 01 0946 to 01 0945
MH: 01 0946MH: 01 0945downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MGO - General Observation - COCKROACHES IN MH0 ft. AMH - Upstream Manhole, Survey Begins - 01 09462 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start10.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start290.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish290.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish292.1 ft. AMH - Downstream Manhole, Survey Ends - 01 0945292.1 ft. MGO - General Observation - COCKROACHES IN MH

Observation photos (4)

  • General Observation - COCKROACHES IN MH

    0 ft. - General Observation - COCKROACHES IN MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    10.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MH

    292.1 ft. - General Observation - COCKROACHES IN MH

Observations (11)

DistanceCodeObservation
10.6CM
2DAGS
0MWM
292.1AMH01 0945
0MWL
290.5DAGS
0MGOCONNECTION AT MH 3 O'CLOCK
0MGOCOCKROACHES IN MH
0AMH01 0946
292.1MGOCOCKROACHES IN MH
290.5CM

Properties (7)

additional_info
SC411257
custom_field_two
3
customer
LACSD
datetime
2020-05-18T02:10:29-07:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
10286