Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 11, 2020, 08:18 AM
  • 01 0980_01 0979_05112020_012609.mp4

Date
05/11/2020
W/O
828917
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00228
PipeID
P01818
Time
1:18 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7657
Sewer Name
01 WRIGHT ROAD TRUNK
City
MAYWOOD
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
05
Purpose
Routine Assessment
Project
RFIR_WO_828917_TV01251_MAY2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
01 0980
Downstream MH
01 0979
Dir. of Survey
Downstream
Length Surveyed
362 ft.
Total Length
362 ft.
Structural Index
3
Structural Quick
3M00
Structural Rating
216
O&M Index
2
O&M Quick
2M00
O&M Rating
144
Overall Index
3
Overall Quick
Overall Rating
360
Pipe schematic from manhole 01 0980 to 01 0979
MH: 01 0980MH: 01 0979downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 09802 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start360.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish360.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish362 ft. MGO - General Observation - CONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK362 ft. AMH - Downstream Manhole, Survey Ends - 01 0979

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
2CM
360.6CM
2DAGS
0MWM
0MWL
362MGOCONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK
360.6DAGS
0AMH01 0980
362AMH01 0979

Properties (6)

additional_info
SC411248
custom_field_two
3
customer
LACSD
datetime
2020-05-11T01:18:01-07:00
documentation
PRO PIPE
is_lateral_inspection
false