Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 14, 2020, 06:33 AM
  • 01 0966_01 0965_05132020_234108.mp4

Date
05/13/2020
W/O
828917
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00228
PipeID
P01803
Time
11:33 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7664
Sewer Name
01 WRIGHT ROAD TRUNK
City
MAYWOOD
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
05
Purpose
Routine Assessment
Project
RFIR_WO_828917_TV01251_MAY2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
01 0966
Downstream MH
01 0965
Dir. of Survey
Downstream
Length Surveyed
195.1 ft.
Total Length
195.1 ft.
Structural Index
2
Structural Quick
2D00
Structural Rating
46
O&M Index
2
O&M Quick
2G00
O&M Rating
76
Overall Index
2
Overall Quick
Overall Rating
122
Pipe schematic from manhole 01 0966 to 01 0965
MH: 01 0966MH: 01 0965downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 09660 ft. MGO - General Observation - CONNECTION AT MH 4 O'CLOCK0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start12.5 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start73.7 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish136.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start193.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish193.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish195.1 ft. MGO - General Observation - COCKROACHES IN MANHOLE195.1 ft. AMH - Downstream Manhole, Survey Ends - 01 0965

Observation photos (5)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    12.5 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    136.4 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    195.1 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (13)

DistanceCodeObservation
0MWM
0AMH01 0966
136.4CL
2DAGS
193.4DAGS
0MGOCONNECTION AT MH 4 O'CLOCK
0MGOCOCKROACHES IN MANHOLE
195.1MGOCOCKROACHES IN MANHOLE
12.5CL
73.7CL
195.1AMH01 0965
193.4CL
0MWL

Properties (7)

additional_info
SC411255
custom_field_two
3
customer
LACSD
datetime
2020-05-13T23:33:34-07:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid