Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 15, 2020, 08:54 AM
  • 18 0765_18 0764 _05152020_023914.mp4

Date
05/15/2020
W/O
828928
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00706
PipeID
P14624
Time
1:54 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7703
Sewer Name
18 SO WHITTIER OUTFALL TR, SECTS 1,2,3,&4
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
20
Purpose
Routine Assessment
Project
RFIR_WO_828928_TV18103_MAY2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
33 in.
Upstream MH
18 0765
Downstream MH
18 0764
Dir. of Survey
Downstream
Length Surveyed
290 ft.
Total Length
290 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 18 0765 to 18 0764
MH: 18 0765MH: 18 0764downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 07650 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK2.1 ft. MGO - General Observation - MAG COAT2.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start174.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"201.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"206.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"290 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK290 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish290 ft. AMH - Downstream Manhole, Survey Ends - 18 0764

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
0AMH18 0765
201.7TF
2.1MGOMAG COAT
0MGOCONNECTION AT MH 9 O'CLOCK
206.9TF
290MGOCONNECTION AT MH 9 O'CLOCK
290SAP
0MWL
290AMH18 0764
2.2SAP
0MWM
0MGOCONNECTION AT MH 3 O'CLOCK
174.1TF

Properties (6)

additional_info
SC411360
custom_field_two
2
customer
LACSD
datetime
2020-05-15T01:54:27-07:00
documentation
PROPIPE
is_lateral_inspection
false