Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 15, 2020, 06:11 AM
  • 18 0749_18 0748 _05142020_233057.mp4

Date
05/14/2020
W/O
828928
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00706
PipeID
P14602
Time
11:11 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7703
Sewer Name
18 SO WHITTIER OUTFALL TR, SECTS 1,2,3,&4
City
WHITTIER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
26
Purpose
Routine Assessment
Project
RFIR_WO_828928_TV18103_MAY2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
18 0749
Downstream MH
18 0748
Dir. of Survey
Downstream
Length Surveyed
407.7 ft.
Total Length
407.7 ft.
Structural Index
4
Structural Quick
5131
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
8
Pipe schematic from manhole 18 0749 to 18 0748
MH: 18 0749MH: 18 0748downstream0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 07490 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start17.9 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - INFREQUENTLY THROUGHOUT407.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish407.7 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK407.7 ft. AMH - Downstream Manhole, Survey Ends - 18 0748407.7 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - INFREQUENTLY THROUGHOUT

    17.9 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - INFREQUENTLY THROUGHOUT

Observations (11)

DistanceCodeObservation
407.7SAP
0MWL
17.9SRVINFREQUENTLY THROUGHOUT
0MGOCONNECTION AT MH 9 O'CLOCK
0MWM
0AMH18 0749
407.7MGOCONNECTION AT MH 9 O'CLOCK
2.1SAP
0MGOCONNECTION AT MH 3 O'CLOCK
407.7AMH18 0748
407.7SRV

Properties (6)

additional_info
SC411360
custom_field_two
2
customer
LACSD
datetime
2020-05-14T23:11:48-07:00
documentation
PROPIPE
is_lateral_inspection
false