Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 15, 2020, 06:50 AM
  • 18 0747_18 0746 _05152020_000611.mp4

Date
05/14/2020
W/O
828928
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00706
PipeID
P14600
Time
11:50 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7703
Sewer Name
18 SO WHITTIER OUTFALL TR, SECTS 1,2,3,&4
City
WHITTIER
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
26
Purpose
Routine Assessment
Project
RFIR_WO_828928_TV18103_MAY2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
18 0747
Downstream MH
18 0746
Dir. of Survey
Downstream
Length Surveyed
387 ft.
Total Length
387 ft.
Structural Index
4
Structural Quick
5131
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
8
Pipe schematic from manhole 18 0747 to 18 0746
MH: 18 0747MH: 18 0746downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 07470 ft. MWM - Water Mark, 35 %of cross sectional area4.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start202.2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - INFREQUENTLY THROUGHOUT387 ft. AMH - Downstream Manhole, Survey Ends - 18 0746387 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish387 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.8 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - INFREQUENTLY THROUGHOUT

    202.2 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - INFREQUENTLY THROUGHOUT

Observations (8)

DistanceCodeObservation
0MWL
387AMH18 0746
4.8SAP
387SAP
0AMH18 0747
202.2SRVINFREQUENTLY THROUGHOUT
387SRV
0MWM

Properties (6)

additional_info
SC411360
custom_field_two
2
customer
LACSD
datetime
2020-05-14T23:50:23-07:00
documentation
PROPIPE
is_lateral_inspection
false