Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 11, 2020, 09:12 AM
  • 18 0730_18 0729 _05112020_022340.mp4

Date
05/11/2020
W/O
828928
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00706
PipeID
P14583
Time
2:12 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7596
Sewer Name
18 SO WHITTIER OUTFALL TR, SECTS 1,2,3,&4
City
WHITTIER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
26
Purpose
Routine Assessment
Project
RFIR_WO_828928_TV18103_MAY2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
33 in.
Upstream MH
18 0730
Downstream MH
18 0729
Dir. of Survey
Downstream
Length Surveyed
307.1 ft.
Total Length
307.1 ft.
Structural Index
4
Structural Quick
5131
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
8
Pipe schematic from manhole 18 0730 to 18 0729
MH: 18 0730MH: 18 0729downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 07300 ft. MWM - Water Mark, 30 %of cross sectional area2.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start4.2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - VERY SPORADIC108.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"268.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"307.1 ft. AMH - Downstream Manhole, Survey Ends - 18 0729307.1 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish307.1 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK307.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.7 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - VERY SPORADIC

    4.2 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - VERY SPORADIC

Observations (11)

DistanceCodeObservation
307.1AMH18 0729
268.4TF
0MWL
2.7SAP
307.1SRV
0AMH18 0730
108.9TFA
4.2SRVVERY SPORADIC
307.1MGOCONNECTION AT MH 9 O'CLOCK
307.1SAP
0MWM

Properties (6)

additional_info
SC411355
custom_field_two
2
customer
LACSD
datetime
2020-05-11T02:12:35-07:00
documentation
PROPIPE
is_lateral_inspection
false