Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 2, 2020, 10:42 AM
  • 08 0521_08 0520a_722020_040640.mp4

Date
07/02/2020
W/O
0828883
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00021
PipeID
P00527
Time
3:42 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1466
Sewer Name
08 VICTORIA STREET TRUNK
City
COMPTON
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
02
Purpose
Capital Improvement Program Assesment
Project
20200701MDM_VICTORIA_STREET_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
08 0520a
Downstream MH
08 0521
Dir. of Survey
Upstream
Length Surveyed
266.2 ft.
Total Length
266.2 ft.
Structural Index
2
Structural Quick
322E
Structural Rating
68
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
70
Pipe schematic from manhole 08 0520a to 08 0521
MH: 08 0520aMH: 08 0521upstream0 ft. AMH - Downstream Manhole, Survey Ends - 5:00AM0.7 ft. MGO - General Observation - MH CONN 9:0 ACTIVE0.7 ft. MGO - General Observation - MH CONN 3:00 STUB5.8 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL18.7 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - SL18.7 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - H35.3 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H51.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H51.5 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL54.8 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - SLIGHT75.5 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - H79.6 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - H91.7 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - SLIGHT99.8 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - SL104.2 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H116.2 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - SL124.3 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - H132.1 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H132.1 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - SL144.5 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL152.9 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SL161.3 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SL161.3 ft. MWM - Water Mark, 30 %of cross sectional area165.4 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - SL169.3 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - SL177.1 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL185.7 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - H201.7 ft. FC - Fracture Circumferential, from 11 to 03 o'clock, within 8 inches of joint: YES - SL204.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 01 to 04 o'clock, , within 8 inches of joint: YES207.3 ft. MGO - General Observation - SLIGHT OFFSETS THROUGHOUT REACH214.1 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - H226.1 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SL229.9 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - SL243.6 ft. RPP - Repair Patch, from 02 to 04 o'clock, within 8 inches of joint: YES - CONCRETE PATCH244.1 ft. FC - Fracture Circumferential, from 11 to 02 o'clock, within 8 inches of joint: YES - SL-CHIPPED246.5 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL253.4 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Active253.8 ft. FC - Fracture Circumferential, from 10 to 11 o'clock, within 8 inches of joint: YES - H254.4 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SL259.9 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - HAIRLINE263.2 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SLIGHT266.2 ft. AMH - Downstream Manhole, Survey Begins - 4:15AM266.2 ft. MWL - Water Level, 10 %of cross sectional area266.2 ft. MWM - Water Mark, 30 %of cross sectional area

Observation photos (3)

  • Fracture Circumferential, from 11 to 02 o'clock, within 8 inches of joint: YES - SL-CHIPPED

    22.1 ft. - Fracture Circumferential, from 11 to 02 o'clock, within 8 inches of joint: YES - SL-CHIPPED

  • Repair Patch, from 02 to 04 o'clock, within 8 inches of joint: YES - CONCRETE PATCH

    22.6 ft. - Repair Patch, from 02 to 04 o'clock, within 8 inches of joint: YES - CONCRETE PATCH

  • General Observation - SLIGHT OFFSETS THROUGHOUT REACH

    58.9 ft. - General Observation - SLIGHT OFFSETS THROUGHOUT REACH

Observations (44)

DistanceCodeObservation
150FCSL
211.4FCSLIGHT
186.6FCH
64.5FCSL
22.1FCSL-CHIPPED
0AMH4:15AM
40.1FCSL
12.8TBActive
265.5MGOMH CONN 9:0 ACTIVE
121.7FCSL
134.1FCH
214.8FLH
89.1FCSL
162FCH
11.8FCSL
141.9FCH
96.9FCSL
0MWL
265.5MGOMH CONN 3:00 STUB
104.9FCSL
0MWM
134.1FCSL
100.8FCSL
113.3FCSL
247.5FCSL
260.4FCSL
22.6RPPCONCRETE PATCH
52.1FCH
80.5FCH
190.7FCH
266.2AMH5:00AM
166.4FCSL
12.4FCH
61.8DAGS
230.9FCH
104.9MWM
6.3FLHAIRLINE
3FCSLIGHT
58.9MGOSLIGHT OFFSETS THROUGHOUT REACH
36.3FCSL
174.5FCSLIGHT
214.7FCSL
19.7FCSL
247.5FCH

Properties (6)

custom_field_three
SLIGHT FRACTURES-REPAIR GOOD COND
custom_field_two
3
customer
LACSD
datetime
2020-07-02T03:42:07-07:00
documentation
MARTIN,SHADLER,BARR
is_lateral_inspection
false